5.10 System Function Instructions

5.10.9 Read Inverter Parameter (ICNS-RD)

5-268

The parameters are described in the following table.

The status configuration is shown below.

Parameter Name

Description

I/O

Read command (Execute)

Reading the Inverter parameters begins when this command turns ON.

IN

Read processing abort command
(Abort)

The read process is aborted when this command turns ON.

IN

Communications device type
(Dev-Typ)

215IF = 1, MP930 = 4, and SVB-01 = 10

IN

Circuit number (Cir-No)

215IF = 1 or 2, MP930 = 1, and SVB-01 = 1 to 16

IN

Slave station number (St-No)

215IF = 1 to 64, MP930 = 1 to 14, and SVB-01 = 1 to 14

IN

Communications buffer channel
number (Ch-No)

215IF = 1 to 3, MP930 = 1, and SVB-01 = 1 to 8

IN

Parameter type (Cns-Typ)

Inverter parameter type:
0 = Direct specification of reference number, 1 = An, 2 = Bn, 3 = Cn,
4 = Dn, 5 = En, 6 = Fn, 7 = Hn, 8 = Ln, 9 = On, and 10 = Tn

IN

Parameter number (Cns-No)

Inverter parameter number (1 to 99)
The upper limit depends on the model of the Inverter.
If the parameter type (Cns-Typ) is set to 0, specify the reference number.

IN

Number of parameters to read
(Cns-Size)

Number of parameters to read from the Inverter (1 to 100)

IN

First address (Dat-Adr)

The first register address of the parameters (MA, DA, or #A).

IN

Reading (Busy)

Turns ON while reading parameters from the Inverter is in progress.

OUT

Read completed (Complete)

Turns ON while reading parameters from the Inverter is completed.

OUT

Error

Turns ON when an error occurs.

OUT

Read execution status (Status)

Inverter parameter read execution status

OUT

Bit

Name

Remarks

0 to 7

Reserved for system.

The error code is given here when an Inverter
response error is received.
01 hex: Function code error
02 hex: Reference number error

8

Execution sequence error

The function will not be executed.

9

Communications parameter error

The function will not be executed.

10

Specified type error

11

Specified number error

The function will not be executed.

12

Specified data error

The function will not be executed.

13

Communications error

The function will not be executed.

14

Inverter response error

The function will not be executed.

15

Address input error

The function will not be executed.