3 ) programming example – Yaskawa MP900 Series Ladder Programming Manual User Manual

Page 309

Advertising
background image

5.10 System Function Instructions

5.10.5 Read Inverter Trace (ITRC-RD)

5-240

The parameters are described in the following table.

The status configuration is shown below.

( 3 ) Programming Example

In the following programming example, trace data is read from an Inverter.
Two records of trace data are read from the Inverter that is connected to station 1 of the SVB–01 on circuit 1. The data
is stored in the area that starts with MW00100.

Parameter Name

Description

I/O

Trace read execution command (Execute)

Reading begins when this command turns ON.

IN

Trace read abort command (Abort)

Reading is aborted when this command turns ON.

IN

Communications device type (Dev-Typ)

215IF = 1, MP930 = 4, and SVB-01 = 10

IN

Circuit number (Cir-No)

215IF = 1 or 2, MP930 = 1, and SVB-01 = 1 to 16

IN

Slave station number (St-No)

215IF = 1 to 64, MP930 = 1 to 14, and SVB-01 = 1 to 14

IN

Communications buffer channel number
(Ch-No)

215IF = 1 to 3, MP930 = 1, and SVB-01 = 1 to 8

IN

Number of records (Rec-Size)

Number of records to read (1 to 64)

IN

Item selection (Select)

Items to read (0001 to FFFF hex)
Bits 0 to F corresponds to trace data items 1 to 26.

IN

First address (Dat-Adr)

First register address to read at source (MA, DA)

IN

Busy

Turns ON while reading Inverter trace data is in progress.

OUT

Complete

Turns ON when reading Inverter trace data is completed.

OUT

Error

Turns ON when an error occurs.

OUT

Status

Inverter trace data read execution status

OUT

Number of records read (Rec-Size)

Number of records that were read

OUT

Read record length (Rec-Len)

Length of records that were read

OUT

Bit

Name

Remarks

0 to 8

Reserved for system.

9

Communications parameter error

The function will not be executed.

10

Reserved for system.

11

Specified number of records error

The function will not be executed.

12

Data storage error

The function will not be executed.

13

Communications error

The function will not be executed.

14

Reserved for system.

15

Address input error

The function will not be executed.