2 indicator status – Yaskawa MP900 Series Ladder Programming Manual User Manual

Page 366

Advertising
background image

7.2 Indicator Status

7-3

T

roubleshooting

7

7.2 Indicator Status

The pattern of the indicators on the MP2000-series Machine Controller shows the operating status. The following table
gives the indicator lighting patterns and corresponding corrective actions.

Class

Indicator Status

Meaning

Corrective Action

RDY RUN ALM

ERR

BAT

Normal

Not

lit.

Not

lit.

Lit.

Lit.

Not

lit.

Hardware has been reset.

Normally, the CPU Unit will start within
10 seconds. If more than 10 seconds is
required, there is an error in a user pro-
gram or a hardware failure.

Not

lit.

Not

lit.

Not

lit.

Not

lit.

Not

lit.

The Machine Controller is being initial-
ized.

Not

lit.

Lit.

Not

lit.

Not

lit.

Not

lit.

Drawing A is being executed.

Lit.

Not

lit.

Not

lit.

Not

lit.

Not

lit.

The user program is stopped.
(The Machine Controller is in Offline
Stopped Mode.)

This status is entered at the following
times. It does not represent an error.

• The stop operation was performed from

the MPE720.

• The STOP switch was turned ON.

Lit.

Lit.

Not

lit.

Not

lit.

Not

lit.

The user programs are being executed
normally.

Normal operation is in progress.

Er

ror

Not

lit.

Not

lit.

Not

lit.

Lit.

Not

lit.

A serious failure, watchdog timer error,
or Module synchronization error has
occurred.

A hardware failure, watchdog timer error,
or Module synchronization error has
occurred.
Refer to 7.3 Problem Classifications.

Not

lit.

Not

lit.

Not

lit.

Flash-

ing.

Not

lit.

A software error occurred.
Number of Flashes

3: Read address error exception
3: Write address error exception
5: FPU exception
6: General illegal instruction exception
7: Slot illegal instruction exception
8: General FPU suppression exception
9: Slot FPU suppression exception
10: TLB multibit exception
11: LTB reading error exception
12: LTB writing error exception
13: LTB read protection violation

exception

14: LTB write protection violation

exception

15: Initial page write exception

A system error occurred.
Refer to 7.4.5 System Errors.

Not

lit.

Not

lit.

Flash

ing.

Flash-

ing.

Not

lit.

A hardware error occurred.
Number of Flashes

2: RAM diagnostic error
3: ROM diagnostic error
4: CPU Function Module diagnostic

error

5: FPU Function Module diagnostic

error

A hardware failure has occurred. Replace
the Module.

Al

arm

Lit.

Battery alarm

Replace the Battery.

Lit.

Lit.

Lit.

Not

lit.

Not

lit.

An operation error occurred.
An I/O error occurred.

• Operation Errors

Refer to 7.4.1 Operation Errors.

• I/O Errors

Refer to 7.4.2 I/O Errors.

Advertising