5.10 System Function Instructions

5.10.3 Trace (TRACE)

5-233

Instructions

5

The parameters are described in the following table.

The status configuration is shown below.

( 3 ) Programming Example

In the following programming example, the definition for trace group number 1 is used to execute a trace. The trace
starts when DB000000 turns ON.

Œ

Set the data trace definition for trace group number 1 on the MPE720 in advance. Make sure to set the sampling
condition to Program.

Parameter Name

Description

I/O

Trace execution command (Execute)

Trace execution begins when this command turns ON.

IN

Trace reset command (Reset)

Trace execution is reset when this command turns ON.

IN

Trace group No. (Group-No)

Trace group No. specification (1 to 4)

IN

Trace end (Trc-End)

Turns ON when the trace ends.

OUT

Error

Turns ON when an error occurs.

OUT

Status

Trace execution status

OUT

Bit

Name

Remarks

0

Trace data full

Turns ON after once going through the data
trace memory of the specified group.

1 to 7

Reserved for system.

8

No trace definition

The function will not be executed.

9

Group No. error

The function will not be executed.

10 to 12

Reserved for system.

13

Execution timing error

The function will not be executed.

14

Reserved for system.

15

Reserved for system.