5.10 System Function Instructions
5.10.6 Send Message (MSG-SND)
5-245
Instructions
5
3.
PARAMETER
If the RESULT is 4 (FMT_NG), one of the following error codes is given. Otherwise, the remote station address
is given.
4.
REQUEST
1 = Request
2 = Reception completed notification
Remote Station Number (PARAM02)/Serial
1 to 254: The message is sent to the station with the specified device address.
Function Code (PARAM04)
Set the MEMOBUS function code to send.
The function codes are listed in the following table.
{
: Can be set,
×: Cannot be set.
When the target device is operating as the master, only MW and MB data can be read and written. When the target
device is operating as a slave, MB, MW, IB, and IW data can be read and written for coils, hold registers, input
relays, and input registers, respectively.
Code
Error
00
No error
01
Station address out of range
02
MEMOBUS response monitoring time error
03
Number of retries setting error
04
Cyclic area setting error
05
Message signal CPU number error
06
Message signal register address error
07
Message signal number of words error
Function Code
Setting
00 hex
Not used.
×
01 hex
Read Coil Status
{
02 hex
Read Input Relay Status
{
03 hex
Read Hold Register Contents
{
04 hex
Read Input Register Contents
{
05 hex
Change Single Coil Status
{
06 hex
Write Single Hold Register
{
07 hex
Not used.
×
08 hex
Loopback Test
{
09 hex
Expanded Read Hold Register Contents
{
0A hex
Expanded Read Input Register Contents
{
0B hex
Expanded Write Hold Register
{
0C hex
Not used.
×
0D hex
Expanded Read Nonconsecutive Hold Registers
{
0E hex
Expanded Write Nonconsecutive Hold Registers
{
0F hex
Change Multiple Coil Status
{
10 hex
Write Multiple Hold Registers
{
11 hex to 20 hex
Not used.
×
21 hex to 3F hex
Reserved for system.
×
40 hex to 4F hex
Reserved for system.
×
50 hex and higher
Not used.
×