5.9 Table Manipulation Instructions

5.9.9 Clear Queue Table Pointers (QTBLCL)

5-224

( 2 ) Format

∗ 1. Optional.
∗ 2. C and # registers cannot be used.

„

Error Codes

( 3 ) Programming Example

In the following programming example, the queue pointers for the specified queue table are initialized when switch 2
(DB000003) turns ON.

When the power is turned ON, values of the read pointer and write pointer are undefined. Always execute the QTBLCL instruc-
tion before using the QTBLR, QTBLRI, QTBLW, or QTBLWI instruction.
An operation error may occur if the QTBLR, QTBLRI, QTBLW, or QTBLWI instruction is executed without first executing the
QTBLCL instruction.

Parameter Name

Applicable Data Types

B

W

L

F

A

Index

Constant

Output data (Out)

*1

×

{

*2

×

×

×

{

×

Status (Sts))

*1

{

*2

×

×

×

×

×

×

Status

Output data

Table name

Icon:

Key entry: QTBLCL

Error Code

Error Name

Meaning

0001 hex

Table undefined

The target table is undefined.

0002 hex

Outside range of row numbers

The row number of the table element is outside the target table.

0003 hex

Outside range of column num-
bers

The column number of the table element is outside the target table.

0004 hex

Incorrect number of elements

The number of target elements is invalid.

0005 hex

Insufficient storage area

The storage area is insufficient.

0006 hex

Insufficient element type

The data type specified for the element is wrong.

0007 hex

Queue buffer error

An attempt was made to read from an empty queue buffer, or to write to a
full queue buffer by advancing the pointer.

0008 hex

Queue table error

The specified table is not a queue table.

0009 hex

System error

An unexpected error was detected in the system during instruction execu-
tion.