5.8 DDC Instructions

5.8.9 Function Generator (FGN)

5-169

Instructions

5

[ b ] Parameter Table Configuration for FGN Instruction with Double-length Integers or Real Numbers

If input value X is a double-length integer, the FGN instruction will be for double-length integers. If input value X is a
real number, the FGN instruction will be for real numbers.
Create the parameter table as shown below.

For the FGN instruction, make sure to set the data so that X

1

< X

2

<

⋅⋅⋅ < X

N

, regardless of whether the parameter table is for

integer data, double-length integer data, or real number data.

Address

Data

Type

Symbol

Name

0

W

N

Number of pairs of X and Y

1

W

Reserved.

2

L/F

X

1

Data X

1

4

L/F

Y

1

Data Y

1

6

L/F

X

2

Data X

2

8

L/F

Y

2

Data Y

2

:

:

:

:

4N - 2

L/F

X

N

Data X

N

4N

L/F

Y

N

Data Y

N

X

1

X

2

X

3

Y

1

Y

2

Y

3

X

N

Y

N

Function generated by setting X

1…N

,

Y

1…N

in the parameter table.