background image

Chapter 4 Explanation of Functions

(2) Overload nitice function
The overload notice function allows you to make the inverter output an overload notice signal before
tripping because of overload.
You can use this function effectively to prevent the machine (e.g., a conveyor)driven by the inverter from
being overloaded and prevent the conveyor from being stopped by the overload protection of the inverter.
To use this function, assign function "03" (OK) or "26" (OL2) to one of the intelligent output terminals [11] to
[15] (C021 to C025) and the alarm relay terminal (C026). (Two types of overload notice signal are available
for output.)

Item

Function code

Data or range of data

Description

00

Enabling the warning output during
acceleration, deceleration, and constant

Overload signal output
mode

C040

01

Enabling the warning output during constant

0.0

Disabling the warning output

Overload level setting

C041

0.1 to "2.0 x rated

current" (A)

Specifying the current at which to output the
OL signal (overload notice advance signal
(1))

0.0

Disabling the warning output

Overload setting (2)

C111

0.1 to "2.0 x rated

current" (A)

Specifying the current at which to output the
OL2 signal (overload notice advance signal
(2))


Overload restriction

setting b022/b025

Overload level setting

C041/C111

Output current

OL/OL2 output











4.2.31 Overcurrent restraint

b027: Overcurrent suppression enable

Related code

The overcurrent restraint function allows you to restrain the
overcurrent that can occur when the output current sharply increases
because of rapid acceleration.
You can enable or disable the function by setting the overcurrent suppression enable (b027).

Item

Function code

Data or range of data

Description

00

Disabling the overcurrent restraint

Overcurrent
suppression enable

b027

01

Enabling the overcurrent restraint


Note: When using the inverter for a lift, disable the overcurrent restraint function. If the overcurrent

restraint functions during the lift operation, the lift may slide down because of insufficient torque.