Chapter 4 Explanation of Functions

4 -

54













4.2.49 Reset (RS) function

ON

ON

MC1

MC2

MC3

FW

CS

ON

ON

ON

MC1

MC2

MC3

FW

CS

ON

ON

ON

OFF

Timing chart for switching from the inverter to the

commercial power supply

Timing chart for switching from the commercial power

supply to the inverter

Inverter output
frequency

Operation

Duration of the interlock of MC2 and
MC3 (0.5 to 1 second)

0.5 to 1 second

Inverter output
frequency

Retry wait time (b003)

Starting with matching frequency

Operation

b003: Retry wait time before motor restart
b007: Restart frequency threshold
C102: Reset mode selection
C103: Restart mode after reset
C001 to C008: Terminal [1] to [8] functions

Related code

The reset function allows you to recover the inverter from a tripped
state.
To perform resetting, press the STOP/RESET key of the digital
operator or turn the RS terminal off.
To use the control circuit terminal for resetting, assign function "18"
(RS) to an intelligent input terminal.
You can select the restart mode to apply after resetting with the restart mode after reset (C103). When
C102 =03, starting with 0 Hz is selected regardless to C103 setting.
If the inverter trips because of overcurrent when it starts the motor with matching frequency, increase the
retry wait time before motor restart (b003).
You can select the alarm reset timing with the reset mode selection (C102). You can also enable the reset
signal to be output only when resetting an error alarm.
The RS terminal can be configured only as an a-contact (NO).
Do not use the RS terminal for the purpose of shutting off the inverter output. The reset operation clears
the electronic thermal and BRD counter data stored in the inverter, and, without this data, the inverter may
be damaged during operation.

Item

Function

code

Data or range of

data

Description

Retry wait time
before motor restart

b003

0.3 to 100. (s)

(See the explanations of the retry after instantaneous power
failure or the retry after trip due to insufficient voltage.)
Time to wait after reset until restarting the motor

Restart frequency
threshold

b007

0.00 to 400.0 (Hz)

(See the explanations of the retry after instantaneous power
failure or the retry after trip due to insufficient voltage.)

00

Resetting the trip when the RS signal is turned on (See
example 1.)
(When operation is normal) Shutting off the inverter output
(When an error has occurred) Resetting the trip

01

Resetting the trip when the RS signal is turned off (See
example 2.)
(When operation is normal) Shutting off the inverter output
(When an error has occurred) Resetting the trip

02

Resetting the trip when the RS signal is turned on (See
example 1.)
(When operation is normal) Disabling the inverter output
(When an error has occurred) Resetting the trip

Reset mode
selection

C102

03

Trip is reset (See example 1)
Internal data is not reset. (see 4.3.13)
(When operation is normal) Disabling the inverter output
(When an error has occurred) Resetting the trip

00

Start with 0 Hz

01

Start with matching frequency (See example 3.)

Restart mode after
reset

C103

02

Restart with input frequency (See example 4.)