Chapter 4 Explanation of Functions

4 - 1

29

(xii) 0B command: This command recalculates the constants set in the inverter.
This command must be issued when the base frequency or the setting of parameter "H***" has been
changed for the RS485 communication.
- Transmission frame
Frame format

STX Station

No.

Command BCC

CR

Description

Data

size

Setting

STX

Control code (Start of TeXt)

1 byte

STX (0x02)

Station No.

Station number of control-target
inverter

2 bytes

01 to 32

Command

Command to be transmitted

2 bytes

0B

BCC

Block check code

2 bytes

XOR of the items from "Station No." to "Data."
See Item (3) of this section.

CR

Control code (Carriage Return)

1 byte

CR (0x0D)


- Response frame
Positive response: See Item (2)-(i) of this section.
Negative response: See Item (2)-(ii) of this section.