Chapter 4 Explanation of Functions

4.2.23 PID function

The PID function allows you to use the inverter for the process
control on fluid flow, airflow, and pressure.
To enable this function, specify "01 lenabled" or "02 inverted data
output enabled" for function "A071".
You can disable the PID function with an external signal during
the PID operation. For this purpose, assign function "23" (PID
terminal: disabling PID operation) to an intelligent input terminal.
Turning the PID terminal on disables the PID function and makes
the inverter perform the normal output.
With the PID function, you can limit the PID output according to
various conditions.
Refer to maximum frequency (4.2.10), frequency limiter (4.2.20),
PID rariation range (A078).

Item

Function code

Data or range of data

Description

00

Disabling the PID operation

01

Enabling the PID operation

PID Function Enable

A071

02

Enabling inverted-data output

PID proportional gain

A072

0.2 to 5.0

Proportional gain

PID integral time constant

A073

0.0 to 3600.(s)

Integrated gain

PID derivative gain

A074

0.00 to 100.0(s) Derivative

gain

PV scale conversion

A075

0.01 to 99.99

Scale for unit conversion of PID feedback
data

00

OI-L: 4 to 20 mA

01

O-L: 0 to 10 V

02 RS485

communication

03

Frequency command as pulse train

PV source setting

A076

10

Operation result (*1)

00

Disabling the inverted output

Output of inverted PID
deviation

A077

01

Enabling the inverted output (deviation
polarity inverted)

PID variation range

A078

0.0 to 100.0(%)

Range of PID data variation with
reference to the target value

00 Invalid
01

O-L : 0-10V

02

OI-L : 4-20mA

PID feed forward selection

A079

03

O2-L : -10-10V

PID deviation level setting

C044

0.0 to 100.0(%)

Level to determine the OD signal output

Off level of feedback
comparison signal

C052

0.0 to 100.0(%)

Level to determine the FBV signal output

Onlevel of feedback
comparison signal

C053

0.0 to 100.0(%)

Level to determine the FBV signal output

(*1) refer 4.2.12 Frequency operation function
(1) Basic configuration of PID control











fs

M

+
-

Kp

(1+ +Td・S)

1

Ti・S

Target value
0 to 10 V
4 to 20 mA

Deviation
(

ε)

Feedback

0 to 10 V

4 to 20 mA

Operation
quantity

Normal control

by the inverter

Transducer

Sensor

+
+

Feed Forward invalid

0-10V
0-20mA
-10-10V

A001: Frequency source setting
A005: [AT] selection
A006: [O2] selection
A071: PID Function Enable
A072: PID proportional gain
A073: PID integral time constant
A074: PID derivative gain
A075: PV scale conversion
A076: PV source setting
A077: Output of inverted PID deviation
A078: PID variation range
A079: PID feed forward selection
d004: Process variable (PV), PID feedback
monitoring
C001 to C008: Terminal [1] to [8] functions
C021 to C025: Terminal [11] to [15] functions
C044: PID deviation level setting
C052: Off level of feedback comparison signal
C053: Onlevel of feedback comparison signal

Related code

Kp: Proportional gain Ti: Integral time Td: Derivative time s: Operator ε: Deviation

4 -

26