Chapter 4 Explanation of Functions

4.3.21 Pulse train frequency input

P055: Pulse-string frequency scale
P056: Time constant of pulse-string frequency filter
P057: Pulse-string frequency bias
P058: Pulse-string frequency limit
A002: Frequency source setting
A076: PV source setting
A141: Operation-target frequency selection 1
A142: Operation-target frequency selection 2

Related code

The pulse train frequency input function allows you to use
the pulse train input via the SAP or SAN terminal as a
frequency command or PID feedback data in each control
mode. (You can use this function in every control mode.)
Specify the input frequency corresponding to the allowable
maximum frequency as the pulse train frequency scale
(P055).
You cannot use the start/end frequency setting function for external analog input together with this
function. To limit the input frequency, specify the desired values for the pulse train frequency bias (P057)
and pulse train frequency limit (P058).

Item

Function code

Data or range of data

Description

Pulse train frequency scale

P055

1.0 to 50.0 (kHz)

Specification of the input frequency
corresponding to the maximum
allowable frequency

Time constant of pulse train
frequency filter

P056

0.01 to 2.00 (s)

Setting of the filter time constant for
the pulse train input

Pulse train frequency bias

P057

-100. to +100. (%)

Pulse train frequency limit

P058

0. to 100. (%)

Frequency source setting

A001

06

PV source setting

A076

03

Operation-target frequency
selection 1

A141 05

Operation-target frequency
selection 2

A142 05

Settings for the frequency input as
a pulse train

Frequency
measurement

÷

Frequency scale
(1.0 to 50.0 kHz)

%

Hz

1+sT

1

×

Frequency
command

Bias

Limit

Bias limitation

Maximum
frequency (F004)

Primary delay filter

Hz

%










Block diagram for pulse train frequency input

4 - 11