2 - 24

2.2.5 Selection and wiring of regenerative braking resistor (on 5.5 kW to 22 kW models)

The SJ700-2 series inverter models with capacities of 5.5 to 22 kW have an internal regenerative braking

circuit.

Connecting an optional regenerative braking resistor to RB and P terminals increases the regenerative

torque.


Without a resistor

connected

With a resistor

connected

Minimum connectable

resistor

Model

Motor capacity

(kW)

Regenerative

torque (%)

Resistanc

e of

connecte
d resistor

(Ω)

Regenera

tive

torque

(%)

Resistanc

e

(Ω)

BRD

usage

rate
(%)

Minimum

resistance during

continuous

operation

(Ω)

SJ700-055LFF2 5.5

20

16 100 16 10

50

SJ700-075LFF2 7.5

20

10 80 10 10

50

SJ700-110LFF2 11

10

10 70 10 10

50

SJ700-150LFF2 15

10

7.5 80 7.5 10

35

SJ700-185LFF2 18.5

10

7.5 60 7.5 10

35

SJ700-220LFF2 22

10

5 50 5 10

35

SJ700-055HFF2 5.5

20

70 100 70 10

200

SJ700-075HFF2 7.5

20

70 80 35 10

150

SJ700-110HFF2 11

10

50 80 35 10

150

SJ700-150HFF2 15

10

35 80 24 10

100

SJ700-185HFF2

18.5

10

35 70 24 10

100

SJ700-220HFF2 22

10

35 50 20 10

100

Advertising