Chapter 4 Explanation of Functions

4 - 152

Register

No.

Function name

Function code

R/W

Monitoring and setting items Data resolution

Register

No.

12B0h

Operation-target frequency
selection 2

A142 R/W

0 (digital operator), 1 (keypad potentiometer), 2
(input via O), 3 (input via OI), 4 (external
communication), 5 (option 1), 6 (option 2), 7 (pulse
train frequency input)

-

12B1h Operator

selection

A143

R/W

0 (addition: A141 + A142), 1 (subtraction: A141 -
A142), 2 (multiplication: A141 x A142)

-

12B2h (Reserved)

-

- Inaccessible

-

12B3h A145

(high)

R/W

12B4h

Frequency to be added

A145 (low)

R/W

0 to 40000

0.01 [Hz]

12B5h

Sign of the frequency to be
added

A146 R/W

00 (frequency command + A145), 01 (frequency
command - A145)

-

12B6h to

12B8h

(Reserved) -

-

Inaccessible

-

12B9h

EL-S-curve
acceleration/deceleration ratio 1

A150

R/W 0 to 50

1 [%]

12BAh

EL-S-curve
acceleration/deceleration ratio 2

A151

R/W 0 to 50

1 [%]

12BBh

EL-S-curve
deceleration/deceleration ratio 1

A152

R/W 0 to 50

1 [%]

12BCh

EL-S-curve
deceleration/deceleration ratio 2

A153

R/W 0 to 50

1 [%]