Chapter 4 Explanation of Functions

4.2.52 External trip (EXT) function

The external trip function allows you to make the inverter trip
according to the error (trip) signal generated by an external system.

C001 to C008: Terminal [1] to [8] functions

Related code

To use this function, assign function "12" (EXT) to one of the terminal [1] to [8] functions (C001 to C008).
When the EXT terminal is turned on, the inverter trips with error code "E12" displayed and stops the
output.
After the inverter trips with error code "E12" displayed, it will not be recovered from tripping, even when the
error signal from the external system is reset (i.e., the EXT terminal is turned off).
To recover the inverter from tripping, reset the inverter or turn the inverter power off and on.

Item Function

code

Data

Description

Terminal [1] to [8] functions

C001 to C008

12

EXT: External trip

Note: Do not turn on the EXT terminal after the inverter power is shut off. Otherwise, the error history may

not be stored correctly.

Operation commands
FW and RV

EXT terminal

Motor speed

RS terminal

Alarm output terminal

Free running











4.2.53 3-wire interface operation function (STA, STP, and F/R)

The 3-wire interface operation function allows you to use automatic-
reset contacts (e.g., pushbutton switches) to start and stop the inverter.

C001 to C008: Terminal [1] to [8] functions

Related code

Specify "01" (control circuit terminal block) for the run command source setting (A002).
Assign function "20" (STA), "21" (STP), and "22" (F/R) to three of the terminal [1] to [8] functions (C001 to
C008) to enable the control operations described below. Assigning the STP function to an intelligent input
terminal disables the functions of the FW and RV terminals.
The figure below shows the inverter outputs according to terminal operations.

Item Function

code

Data

Description

20

STA: Starting the motor

21

STP: Stopping the motor

Terminal [1] to [8] functions

C001 to C008

22

F/R: Switching the motor operation
direction

Output frequency

OFF

OFF

ON

ON

F/R

STP

STA

Forward
rotation

Reverse
rotation