Chapter 4 Explanation of Functions

4 -

75

4.2.83 Initialization setting

Function

code

b084: Initialization mode (parameters
or trip history)
b085: Country code for initialization

Related code

The initialization function allows you to initialize the adjusted settings on
the inverter to restore the factory settings. You can also clear the trip
history data alone.
The settings of initialization are described below.
The settings of "P100" to "P131", running-time data, and power-on time data cannot be cleared.

Item

Data

Description

00

Clearing on the trip history data

01

Initializing only the settings
The factory settings are restored.

Initialization mode
(parameters or trip
history)

b084

02

Clearing the trip history data and initializing the
settings

00

Defaults intended for Japan

01

Defaults intended for Europe

Country code for
initialization

b085

02

Defaults intended for the U.S.A.


(Initializing procedure)
Adjust the above settings as required, and then perform the following procedure:

RUN

STOP/

RESET

RUN

STOP/

RESET

RUN

STOP/

RESET

FUNC

STR

FUNC

STR

FUNC

STR




Note 2: The initialization operation does not initialize the settings of easy sequence user parameters

(P100 to P131).

1) Holding down the FUNC and [2]

(down) keys, press and hold down
the STOP/RESET key.
- After the monitor starts blinking,

release only the STOP/RESET
key. (The display on the monitor
changes to that shown in the
middle figure above.

- Release the FUNC and [2]

(down) keys.

2) Initialization is in progress.
- The above figure shows the

monitor display (indicating that the
initialization is in progress)
intended for Japan. Those
intended for other regions and trip
history clearance are shown
below.

3) When the initialization is

completed, the monitor displays
code "d001".

Confirm that the settings have

been initialized.

Initialization-in-progress
display intended for Europe

Initialization-in-progress display for
trip history clearance

In the far-left digit, the lighting
segments move round for

Initialization-in-progress
display intended for the U.S.A.
















Note 1: The initialization operation does not initialize the analog input settings (C081, C082, C083, C121,

C122, and C123) and thermistor coefficient setting (C085).