Chapter 4 Explanation of Functions

4.2.37 Dynamic braking (BRD) function

4 -

45

The dynamic braking (BRD) function is provided in the
SJ700-220LFF/HFF and other models that have the built-in BRD circuit.
With this function, the energy regenerated by the motor is consumed by
an external resistor (i.e., the energy is converted to heat). You can
effectively use this function in your system, for example, to operate the
motor as a generator by rapidly decelerating the motor.

b090: Dynamic braking usage ratio
b095: Dynamic braking control
b096: Dynamic braking activation level

Related code

To use this function, make the following settings:

Item

Function code

Data or range of data

Description

0.0

Disabling the BRD operation

Dynamic braking
usage ratio

b090 (*2)

0.1 to 100.0 (%)

Setting of the dynamic braking usage ratio in units
of 0.1%
The inverter will trip when the set rate is exceeded.







Usage rate (%) =

× 100

00

Disabling the BRD operation

01

Enabling the BRD operation while the motor is
running
Disabling the BRD operation while the motor is
stopped

Dynamic braking
control

b095

02

Enabling the BRD operation regardless of whether
the motor is running

330 to 380 (V) (*1)

Level setting for 200 V class models

Dynamic braking
activation level

b096

660 to 760 (V) (*1)

Level setting for 400 V class models

*1 The set dynamic braking activation level specifies the DC output voltage of the inverter's internal
converter.

*2 Please refer P2-22 for minimum resistance of connectable resistor and BRD ratio (2.2.5).

4.2.38 Cooling-fan operation setting

The cooling-fan operation setting function allows you to specify the
operation mode of the inverter's internal cooling fan. The cooling fan can
be operated on a constant basis or only while the inverter is driving the
motor.

t2

ON

t1

t3

ON

ON

BRD
operation

100 seconds

100 seconds

(t1+t2+t3)

b092: Cooling fan control

Related code

Item

Function code

Data or range of data

Description

00

Specifying that the fan operates on a constant basis

Cooling fan
control

b092

01

Specifying that the fan operates only while the
inverter is driving the motor.
Note that the fan operates for 5 minutes after the
inverter power is turned on and after the inverter is
stopped.

Note: The cooling fan stops automatically when instantaneous power failure occurs or the inverter power is

shut off and resume the operation after power recovered.