Chapter 4 Explanation of Functions

4.1.8 Actual-frequency monitoring

d008: Actual-frequency monitoring
P011: Encoder pulse-per-revolution
(PPR) setting
H004: Motor poles setting, 1st motor
H204: Motor poles setting, 2nd motor

Related code

The actual-frequency monitoring function is effective only when a motor
equipped with an encoder is connected to the inverter and the feedback
option board (SJ-FB) is mounted in the inverter. When the
actual-frequency monitoring function (d008) is selected, the inverter
displays the actual operating frequency of the motor (regardless of the
motor control method (A044 or A244)).
(Display)

Forward operation:

0.00 to 99.99 in steps of 0.01 Hz
100.0 to 400.0 in steps of 0.1 Hz

Reverse operation:

- 0.0 to -99.9 in steps of 0.1 Hz
- 100 to -400 in steps of 1 Hz

Note:

To use this monitoring function, set the encoder pulse-per-revolution (PPR) setting (P011) and the
number of motor poles (H004 or H204) correctly.

4 -

3

4.1.9 Torque command monitoring

The torque command monitoring function is effective when you have
selected control by torque for the vector control with sensor. When the
torque command monitoring function (d009) is selected, the inverter
displays the value of the currently input torque command.
The % monitor lamp lights up while the inverter is displaying the torque command value.

d009: Torque command monitoring
P033: Torque command input selection
P034: Torque command setting
A044:

V/f characteristic curve selectcion

C001 to C008: Terminal [1] to [8]

Related code

Assign 52 (ATR) on intelligent input terminal and turn on to activate torque control.
(Display)

0. to 200. in steps of 1 %

4.1.10 Torque bias monitoring

The torque bias monitoring function is effective when you have selected
the vector control with sensor. When the torque bias monitoring function
(d010) is selected, the inverter displays the value of the currently set
value of torque bias.
The % monitor lamp lights up while the inverter is displaying the torque bias value.

d010: Torque bias monitoring
A044:

V/f characteristic curve selectcion

P036: Torque bias mode
P037: Torque bias value
P038: Torque bias polarity

Related code

(Display)

-150. to +150. in steps of 1 %

4.1.11 Torque monitoring

When the torque monitoring function (d012) is selected, the inverter
displays the estimated value of the torque output from the inverter.
The % monitor lamp lights up while the inverter is displaying the estimated output torque.

Related code

d012: Torque monitoring
A044:

V/f characteristic curve selectcion

(Display)

-300. to +300. in steps of 1 %

Note: This monitoring function is effective only when you have selected the sensorless vector control,

0Hz-range sensorless vector control, or vector control with sensor as the control mode.

Displayed value is not accurate when the other control method is selected.

4.1.12 Output voltage monitoring

d013: Output voltage monitoring

Related code

When the output voltage monitoring function (d013) is selected, the
inverter displays the voltage output from the inverter.
The V monitor lamp lights up while the inverter is displaying the output voltage.
(Display)

0.0 to 600.0 in steps of 0.1 V

(remark) Displayed value may not be accurate when the output voltage is differ from input voltage.

4.1.13 Power monitoring

d014: Power monitoring

Related code

When the power monitoring function (d014) is selected, the inverter
displays the electric power (momentary value) input to the inverter.
The kW monitor lamps (V and A lamps) light up while the inverter is displaying the input power.
(Display)

0.0 to 999.9 in steps of 0.1 kW