Chapter 4 explanation of functions – Hitachi SJ700-2 User Manual

Page 216

Advertising
background image

Chapter 4 Explanation of Functions

4 - 153

Register

No.

Function name

Function

code

R/W

Monitoring and setting items Data resolution

Register

No.

1301h

Selection of restart mode

b001

R/W

0 (tripping), 1 (starting with 0 Hz), 2 (starting with
matching frequency), 3 (tripping after deceleration
and stopping with matching frequency), 4 (restarting
with active matching frequency)

-

1302h

Allowable under-voltage power
failure time

b002

R/W 3 to 250

0.1 [sec.]

1303h

Retry wait time before motor
restart

b003

R/W 3 to 1000

0.1 [sec.]

1304h

Instantaneous power
failure/under-voltage trip alarm
enable

b004 R/W

0 (disabling), 1 (enabling), 2 (disabling during
stopping and decelerating to stop)

-

1305h

Number of restarts on power
failure/under-voltage trip events

b005

R/W 0 (16 times), 1 (unlimited)

-

1306h

Phase loss detection enable

b006

R/W 0 (disabling), 1 (enabling)

-

1307h b007

(high)

R/W

1308h

Restart frequency threshold

b007 (low)

R/W

0 to 40000

0.01 [Hz]

1309h

Selection of retry after tripping

b008

R/W

0 (tripping), 1 (starting with 0 Hz), 2 (starting with
matching frequency), 3 (tripping after deceleration
and stopping with matching frequency), 4 (restarting
with active matching frequency)

-

130Ah

Selection of retry count after
undervoltage

b009

R/W 0 (16 times), 1 (unlimited)

-

130Bh

Selection of retry count after
overvoltage or overcurrent

b010

R/W 1 to 3

1 [time]

130Ch

Retry wait time after tripping

b011

R/W 3 to 1000

0.1 [sec.]

130Dh

Electronic thermal setting
(calculated within the inverter
from current output)

b012

R/W 200 to 1000

0.1 [%]

130Eh

Electronic thermal characteristic

b013

R/W

0 (reduced-torque characteristic), 1 (constant-torque
characteristic), 2 (free setting)

-

130Fh (Reserved)

-

- Inaccessible

-

1310h

Free setting, electronic thermal
frequency (1)

b015

R/W 0 to 400

1 [Hz]

1311h

Free setting, electronic thermal
current (1)

b016

R/W 0 to Rated current

0.1 [A]

1312h

Free setting, electronic thermal
frequency (2)

b017

R/W 0 to 400

1 [Hz]

1313h

Free setting, electronic thermal
current (2)

b018

R/W 0 to Rated current

0.1 [A]

1314h

Free setting, electronic thermal
frequency (3)

b019

R/W 0 to 400

1 [Hz]

1315h

Free setting, electronic thermal
current (3)

b020

R/W 0 to Rated current

0.1 [A]

1316h

Overload restriction operation
mode

b021 R/W

0 (disabling), 1 (enabling during acceleration and
constant-speed operation), 2 (enabling during
constant-speed operation), 3 (enabling during
acceleration and constant-speed operation [speed
increase at regeneration])

-

1317h

Overload restriction setting

b022

R/W 200 to 2000

0.1 [%]

1318h

Deceleration rate at overload
restriction

b023

R/W 10 to 3000

0.01

[

sec.]

1319h

Overload restriction operation
mode (2)

b024 R/W

0 (disabling), 1 (enabling during acceleration and
constant-speed operation), 2 (enabling during
constant-speed operation), 3 (enabling during
acceleration and constant-speed operation [speed
increase at regeneration])

-

131Ah

Overload restriction setting (2)

b025

R/W 200 to 2000

0.1 [%]

131Bh

Deceleration rate at overload
restriction (2)

b026

R/W 10 to 3000

0.01

[

sec.]

131Ch

Overcurrent suppression enable

b027

R/W 0 (disabling), 1 (enabling)

-

131Dh

Active frequency matching scan
start frequency

b028

R/W 200 to 2000

0.1 [%]

131Eh

Active frequency matching,
scan-time constant

b029

R/W 10 to 3000

0.01

[

sec.]

131Fh

Active frequency matching,
restart frequency select

b030 R/W

0 (frequency at the last shutoff), 1 (maximum
frequency), 2 (set frequency)

-

1320h

Software lock mode selection

b031

R/W

0 (disabling change of data other than "b031" when
SFT is on), 1 (disabling change of data other than
"b031" and frequency settings when SFT is on), 2
(disabling change of data other than "b031"), 3
(disabling change of data other than "b031" and
frequency settings), 10 (enabling data changes
during operation)

-

1322h (Reserved)

-

- Inaccessible

-

1323h b034

(high)

R/W

1324h

Run/power-on warning time

b034 (low)

R/W

0 to 65535

1 [10h]