Chapter 4 Explanation of Functions

4.2.58 Intelligent output terminal setting

C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function

Related code

You can assign the functions described below to the intelligent
output terminals [11] to [15] (C021 to C025) and the alarm relay
terminal (C026).
The intelligent output terminals [11] to [15] are used for open-collector output, and the alarm relay terminal
is used for relay output.
You can select the a-contact or b-contact output for individual output terminals by using functions "C031" to
"C035" and "C036".
When "01" (3 bits) or "02" (4 bits) is specified for the alarm code output "C062" (see Section 4.2.65), the
alarm code output is assigned to output terminals 11 to 13 or output terminals 11 to 14 (AC0 to AC3),
respectively. Subsequently, the settings of "C021" to "C024" are invalidated.

Data Description

Reference

item

Page

00

RUN: Running signal

Running signal (RUN)

4-62

01

FA1: Constant-speed reached

02

FA2: Set frequency overreached

Frequency-arrival signals

4-62

03

OL: Overload notice advance signal (1)

Overload restriction/overload notice advance signal

4-40

04

OD: Output deviation for PID control

PID function

4-26

05

AL: Alarm signal

Protective functions

06

FA3: Set frequency reached

Frequency-arrival signals

4-62

07

OTQ: Over-torque

Over-torque signal

4-65

08

IP: Instantaneous power failure

09 UV:

Undervoltage

Instantaneous power failure/undervoltage

4-35

10 TRQ:

Torque

limited

Torque limitation function

4-92

11

RNT: Operation time over

Operation time over signal

4-64

12

ONT: Plug-in time over

Plug-in time over signal

4-64

13

THM: Thermal alarm signal

Electronic thermal protection

4-37

19

BRK: Brake release

20

BER: Brake error

Brake control function

4-81

21

ZS: 0 Hz detection signal

0 Hz detection signal

4-64

22

DSE: Speed deviation maximum

V2 control mode selection function

4-96

23

POK: Positioning completed

Orientation function

4-104

24

FA4: Set frequency overreached 2

25

FA5: Set frequency reached 2

Frequency-arrival signals

4-62

26

OL2: Overload notice advance signal (2)

Overload restriction/overload notice advance signal

4-39

27

Odc: Analog O disconnection detection

28

OIDc: Analog OI disconnection detection

29

O2Dc: Analog O2 disconnection detection

4-71

Window comparators function

31

FBV: PID feedback comparison

PID function

4-26

32

NDc: Communication line disconnection

RS485

4-67

33

LOG1: Logical operation result 1

34

LOG2: Logical operation result 2

35

LOG3: Logical operation result 3

36

LOG4: Logical operation result 4

37

LOG5: Logical operation result 5

38

LOG6: Logical operation result 6

Logical operation function

4-66

39

WAC: Capacitor life warning

Capacitor life warning

4-67

40

WAF: Cooling-fan speed drop

Cooling-fan speed drop

4-68

41

FR: Starting contact signal

Starting contact signal

4-68

42

OHF: Heat sink overheat warning

Heat sink overheat warning

4-68

43

LOC: Low-current indication signal

Low-current indication signal

4-69

44

M01: General output 1

45

M02: General output 2

46

M03: General output 3

47

M04: General output 4

48

M05: General output 5

49

M06: General output 6

Easy sequence function

50

IRDY: Inverter ready

Inverter ready signal

4-69

51

FWR: Forward rotation

Forward rotation signal

4-69

52

RVR: Reverse rotation

Reverse rotation signal

4-70

4 -

60

Advertising