Chapter 4 Explanation of Functions

4.3.16 Zero-return function (ORG, ORL)

- One of three types of zero-return operations can be selected by zero-return mode selection (P068).
When a zero-return operation ends, the current position counter is cleared (to 0).
- Use zero-return direction selection (P069) to select the direction of zero-return operation.
- If zero-return operation is not performed, position control is performed based on the assumption that the
motor position detected at power-on is the origin.

<1> Low-speed zero-return

Output frequency

(2)

(1)

ON

ON

(3)

Origin

Low-speed zero-return speed
(P070)

ORL terminal

ORG terminal

(1) The inverter accelerates the motor for

the specified acceleration time to the

low-speed zero-return speed.

(2) The inverter runs the motor at the

low-speed zero-return speed.

(3) The inverter performs positioning

when the ORL signal is input.


Position


<2> High-speed zero-return

<1> The inverter accelerates the motor

for the specified acceleration time to

the high-speed zero-return speed.

ON

ON

ORL terminal

O

ORG terminal

(1)

(2)

(3)

(4)

(5)

High-speed zero-return
speed (P071)

Origin

Position

Output frequency

Low-speed zero-return speed
(P070)

<2> The inverter runs the motor at the

high-speed zero-return speed.

<3> The inverter starts deceleration

when the ORL signal is turned on.

<4> The inverter runs the motor in the

reverse direction at the low-speed

zero-return speed.

<5> The inverter performs positioning

when the ORL signal is turned off.

<3> High-speed zero-return 2

<1> The inverter accelerates the

motor for the specified acceleration

time to the high-speed zero-return

speed.

ON

ON

ORL terminal

ORG terminal

(1)

(2)

(3)

(4)

(5)

(6) (7)

high-speed zero-return speed

(P071)

Origin

Position

Output frequency

Low-speed zero-return speed

(P070)

<2> The inverter runs the motor at the

high-speed zero-return speed.

<3> The inverter starts deceleration

when the ORL signal is turned on.

<4> The inverter runs the motor in the

reverse direction at the low-speed

zero-return speed.

<5> The inverter starts deceleration

when the ORL signal is turned off.

<6> The inverter runs the motor in the

forward direction at the low-speed

zero-return speed.

Z pulse

<7> The inverter performs positioning at the first Z pulse position after the ORL signal is turned on.




4 - 11