Chapter 4 Explanation of Functions

(iii) Writing data to a specified coil [05h]

This function writes data to a specified coil

The following table shows the updating of the coil status.

Coil status

OFF→ON ON→OFF

Updating data (upper digit)

FFh

00h

Updating data (lower digit)

00h

00h

(Example)
When sending an operation command to the inverter at slave address "10":
To start the inverter operation, "03" must be set in parameter "A002". Coil 1 is used to turn on an
operation command.

4 - 138

Query

Field name

Sample setting
(hexadecimal)

1

Slave address (*1)

0A

2 Function

code

05

3

Starting coil number
(upper digit) (*2)

00

4

Starting coil number
(lower digit) (*2)

00

5

Updating data (upper digit)

FF

6

Updating data (lower digit)

00

7

CRC-16 code (upper digit)

8D

8

CRC-16 code (lower digit)

41

If this query is broadcasted, no inverter will return any
response.
Note that the starting coil number is 1 less than the
actual coil number of the coil to be read first.

Response

Field name

Sample setting
(hexadecimal)











*1


*2


If the function to write data to a coil cannot be executed normally, the inverter will return an exception
response. For details, see Item (viii), "Exception response."

(iv) Writing data to a specified register [06h]
This function writes data to a specified register.

(Example)
When setting "50 Hz" as the base frequency setting (A003) in the inverter at slave address "5":
Since register "1203h" to store the base frequency setting (A003) has a data resolution of 1 Hz, specify
"50" (0032h) as the updating data to set "50 Hz".

1 Slave

address

0A

2 Function

code

05

3

Starting coil number (upper
digit)

00

4

Starting coil number (lower
digit)

00

5

Updating data (upper digit)

FF

6

Updating data (lower digit)

00

7

CRC-16 code (upper digit)

8D

8

CRC-16 code (lower digit)

41

y

Field name

Sample setting
(hexadecimal)


Quer

1

Slave address (*1)

05

2 Function

code

06

3

Starting register number
(upper digit) (*2)

12

4

Starting register number
(lower digit) (*2)

02

5

Updating data (upper digit)

00

6

Updating data (lower digit)

32

7

CRC-16 code (upper digit)

AD

8

CRC-16 code (lower digit)

23

If this query is broadcasted, no inverter will return any
response.
Note that the starting coil number is 1 less than the
actual coil number of the coil to be read first.

Response

Field name

Sample setting
(hexadecimal)

1 Slave

address

05

2 Function

code

06

3

Starting register number
(upper digit)

12

4

Starting register number
(lower digit)

02

5

Updating data (upper digit)

00

6

Updating data (lower digit)

32

7

CRC-16 code (upper digit)

AD

8

CRC-16 code (lower digit)

23











*1


*2


If the function to write data to a specified register cannot be executed normally, the inverter will return an
exception response. For details, see Item (viii), "Exception response."