Chapter 4 explanation of functions – Hitachi SJ700-2 User Manual

Page 227

Advertising
background image

Chapter 4 Explanation of Functions

4 - 164

Register

No.

Function name

Function code

R/W

Monitoring and setting items Data

resolution

Register

No.

1681h

Easy sequence user parameter U (27)

P127

R/W 0 to 65530

1

1682h

Easy sequence user parameter U (28)

P128

R/W 0 to 65530

1

1683h

Easy sequence user parameter U (29)

P129

R/W 0 to 65530

1

1684h

Easy sequence user parameter U (30)

P130

R/W 0 to 65530

1

1685h

Easy sequence user parameter U (31)

P131

R/W 0 to 65530

1

1686h to

2102h

(Reserved) -

-

Inaccessible

-



*1 The following table lists the code data for parameter "H003" (motor capacity selection):

Code

data

00 01 02 03 04 05 06 07 08 09 10

Japan or U.S.A. mode

(b085 = 00 or 02)

0.2

kW

- 0.4 - 0.75 - 1.5

2.2 - 3.7 -

EU mode (b085 = 01)

0.2 kW 0.37

- 0.55

0.75

1.1 1.5 2.2 3.0 - 4.0

Code

data

11 12 13 14 15 16 17 18 19 20 21

Japan or U.S.A. mode

(b085 = 00 or 02)

5.5

kW

7.5 11 15 18.5 22 30 37 45 55 75

EU mode (b085 = 01)

5.5 kW 7.5

11

15

18.5

22

30

37

45

55

75

Advertising