Chapter 4 Explanation of Functions

4.2.27 Retry or trip after instantaneous power failure

b001: Selection of restart mode
b002: Allowable under-voltage power failure time
b003: Retry wait time before motor restart
b004: Instantaneous power failure/under-voltage
trip alarm enable
b005: Number of restarts on power
failure/under-voltage trip events
b007: Restart frequency threshold
b008: Selection of retry count after undervoltage
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function

Related code

(1) Retry (restart) after instantaneous power failure
You can select tripping or retrying (restarting) the motor
operation as the inverter operation to be performed at the
occurrence of instantaneous power failure or undervoltage.
If you specify a retry operation for the selection of restart mode
(b001), the inverter will retry the motor operation for the number
of times set as "b005" after an instantaneous power failure or
the number of times set as "b009" after overvoltage
respectively, and then trip if all retries fail. (The inverter will not
trip if you specify an unlimited number of retries.)
With function "b004" you can select whether to make the inverter trip when an instantaneous power failure
or undervoltage occur while the inverter is in a stopped state.
When selecting a retry operation, also set the retry conditions listed below according to the system to be
driven by the inverter.
Even during a retry operation, the inverter will trip with error code "E09" (undervoltage) displayed if the
undervoltage status continues for 40 seconds.

Item Function

code

Data or range of

data

Description

00 Tripping
01

Restarting the motor with 0 Hz at retry

02

Starting the motor with a matching frequency at retry
(See example 1.) (*3)

03

Starting the motor with a matching frequency at retry
The inverter trips after decelerating and stopping the
motor. (*1) (*3)

Selection of restart mode
(*4) (*6)

b001

04

Restarting the motor with an input frequency at retry
(See example 1.) (*3)

Allowable under-voltage
power failure time

b002

0.3 to 25.0 (s)

Restarting the motor when the power failure duration does
not exceed the specified time (See example 1.)
Tripping when the power failure duration exceeds the
specified time (See example 2.)

Retry wait time before
motor restart

b003

0.3 to 100. (s)

Time to wait until restarting the motor

00

Disabling the inverter from tripping

01

Enabling the inverter to trip

Instantaneous power
failure/under-voltage trip
alarm enable (*2) (*4)

b004

02

Disabling the inverter from tripping when the inverter is
stopped or while the motor is being decelerated or
stopped after the operation command has been turned off

00

Retrying the motor operation up to 16 times after
instantaneous power failure

Number of restarts on
power failure/under-voltage
trip events

b005

01

Retrying the motor operation an unlimited number of times
after instantaneous power failure

Restart frequency threshold

b007

0.00 to 400.0 (Hz)

Restarting the motor with 0 Hz if the frequency becomes
less than the frequency set here during motor free-running
(See examples 3 and 4.)

00 Tripping
01

Restarting the motor with 0 Hz at retry

02

Starting the motor with a matching frequency at retry

03

Starting the motor with a matching frequency at retry
The inverter trips after decelerating and stopping the
motor.

Trip/retry selection

b008

04

Restarting the motor with an input frequency at retry

00

Retrying the motor operation up to 16 times after
undervoltage

Selection of retry count
after undervoltage

b009

01

Retrying the motor operation an unlimited number of times
after undervoltage

Selection of retry count
after overvoltage or
overcurrent

b010

1 to 3 (times)

Number of retries to be made after the occurrence of
overvoltage or overcurrent (*5)

Retry wait time after
overvoltage or overcurrent

b011

0.3 to 100. (s)

Time to wait until restarting the motor

00

Frequency set when the inverter output has been shut off

01 Maximum

frequency

Active frequency matching,
restart frequency select

b030

02

Newly set frequency

Active frequency matching,
scan start frequency

b028

"0.20 x rated

current" to "2.00 x

rated current"

Current limit for restarting with active matching frequency

Active frequency matching,
scan-time constant

b029

0.10 to 30.00 (s)

Duration of frequency lowering when restarting with active
matching frequency

4 - 3