Chapter 4 Explanation of Functions

(iv) Error check code

The Modbus-RTU protocol uses the cyclic redundancy check (CRC) as the error check method.

The CRC code is the 16-bit data generated for a data block that has an arbitrary data length (in units
of 8 bits).

A generative polynomial for CRC-16 (X

16

+ X

15

+ X

2

+ 1) is used to generate the CRC code.

Example of CRC-16 calculation

4 - 134

CRC

*1

= FFFFh

CRC-16

operation

Is the target
data found?

Set the XOR of CRC*1 data and

target data in CRC*1

Does any

bit remain after 8-bit

shifting?

Shift CRC*1 to the left by 1 bit

Is the

bit put out of

CRC*1 "1"?

Replace the Hi and Lo bytes

of CRC*1 with each other

End

Set the XOR of CRC*1 data

and A001h in CRC*1

Yes

No

No

Yes

Yes

No

Hi

Lo

CRC register (2 bytes)

CRC

*1

The target data is shifted by 1 byte.


(v) Header and trailer (silent interval)

The header and trailer set the total time the inverter should wait before sending a response after
having received a query from the master system.

Be sure to specify the time corresponding to the transmission of 3.5 characters (24 bits) as the
waiting time. If a shorter waiting time (corresponding to the transmission of fewer than 3.5 characters)
is specified, the inverter will not respond.

The actual waiting time is the sum of the silent interval (corresponding to the transmission of 3.5
characters) and the communication wait time (C078).