Safety Instructions

9. This Instruction Manual indicates the sizes of the distribution fuse and circuit breaker that must be

connected to this inverter. The following table lists the inverse time and current ratings of the circuit

breakers (with rated voltage of 600 V) to be connected to the individual inverter models:

Model No.

Fuse/circuit breaker (A)

Type

Rating

SJ700-055LFF2 Inverse

time

30

A

SJ700-075LFF2 Inverse

time

40

A

SJ700-110LFF2 Inverse

time

60

A

SJ700-150LFF2 Inverse

time

80

A

SJ700-185LFF2 Inverse

time

100

A

SJ700-220LFF2 Inverse

time

125

A

SJ700-300LFF2 Inverse

time

150

A

SJ700-370LFF2 Inverse

time

175

A

SJ700-450LFF2 Inverse

time

225

A

SJ700-550LFF2 Inverse

time

250

A

SJ700-055HFF2 Inverse

time

40

A

SJ700-075HFF2 Inverse

time

40

A

SJ700-110HFF2 Inverse

time

40

A

SJ700-150HFF2 Inverse

time

40

A

SJ700-185HFF2 Inverse

time

50

A

SJ700-220HFF2 Inverse

time

60

A

SJ700-300HFF2 Inverse

time

70

A

SJ700-370HFF2 Inverse

time

90

A

SJ700-450HFF2 Inverse

time

125

A

SJ700-550HFF2 Inverse

time

125

A

10. Field wiring of the inverter must incorporate UL-listed, CSA-certified closed-loop terminal connectors

that match the wire gauge in terms of size. The crimping tool specified by the connector manufacturer

must be used to secure each connector.