Chapter 4 Explanation of Functions

(4) Explanation of function codes

(i) Reading the coil status [01h]
This function reads the coil status (on or off).

(Example)
When reading the status of the intelligent input terminals [1] to [6] of the inverter at slave address "8":
Assume that the intelligent input terminals are in the status as shown below.

Intelligent

input

terminal

1 2 3 4 5 6

Coil

number

7 8 9 10 11 12

Terminal

status

ON ON ON OFF ON OFF

Coils 13 and 14 are off.

Query

Field name

Sample setting
(hexadecimal)

1

Slave address (*1)

08

2 Function

code

01

3

Starting coil number
(upper digit) (*2)

00

4

Starting coil number
(lower digit) (*2)

06

5

Number of coils (upper digit)
(*3)

00

6

Number of coils (lower digit)
(*3)

06

7

CRC-16 code (upper digit)

5C

8

CRC-16 code (lower digit)

90

*1 This query cannot be broadcasted.
*2 Note that the starting coil number is 1 less than the

actual coil number of the coil to be read first.

*3 If 0 or a value more than 32 is specified as the number

of coils to be read, the inverter will respond with error
code "03h".

Response

Field name

Sample setting
(hexadecimal)

1 Slave

address

08

2 Function

code

01

3

Number of data bytes

01

4

Coil data (*4)

17

5

CRC-16 code (upper digit)

12

6

CRC-16 code (lower digit)

1A

*4 The data as many as the specified number of data

bytes is transferred.























The data received in the response indicates the status of coils 7 to 14. Read the received data (17h =
00010111b) as shown below. The least-significant bit indicates the status of coil 7.

Coil

number

14 13 12 11 10 9 8 7

Coil

status OFF OFF OFF ON OFF ON ON ON


If the query has specified the reading of an undefined coil, the data on the said coil is represented by "0"
in the response.
If the function to read the coil status cannot be executed normally, the inverter will return an exception
response. For details, see Item (viii), "Exception response."

4 - 136