Chapter 4 explanation of functions – Hitachi SJ700-2 User Manual

Page 229

Advertising
background image

Chapter 4 Explanation of Functions

4 - 166

Register

No.

Function name

Function code

R/W

Monitoring and setting items Data resolution

Register

No.

230Ch

Electronic thermal setting
(calculated within the inverter
from current output), 2nd
motor

b212 R/W

200 to 1000

0.1 [%]

230Dh

Electronic thermal
characteristic, 2nd motor

b213 R/W

0 (reduced-torque characteristic), 1 (constant-
torque characteristic), 2 (free setting)

-

230Eh to

2501h

(Reserved) -

-

Inaccessible

-

2502h

Motor data selection, 2nd
motor

H202 R/W

0 (Hitachi standard data), 1 (auto-tuned data), 2
(auto-tuned data [with online auto-tuning function])

0.1 [%]

2503h

Motor capacity, 2nd motor

H203

R/W (*1)

-

2504h

Motor poles setting, 2nd motor

H204

R/W

0 (2 poles), 1 (4 poles), 2 (6 poles), 3 (8 poles), 4
(10 poles)

-

2505h H205

(high)

R/W

2506h

Motor speed constant, 2nd
motor

H205 (low)

R/W

1 to 80000

0.001

2507h

Motor stabilization constant,
2nd motor

H206 R/W

0 to 255

1

2508h to

2514h

(Reserved) -

-

Inaccessible

-

2515h H220

(high)

R/W

2516h

Motor constant R1, 2nd motor

H220 (low)

R/W

1 to 65530

0.001 [Ω]

2517h H221

(high)

R/W

2518h

Motor constant R2, 2nd motor

H221 (low)

R/W

1 to 65530

0.001 [Ω]

2519h H222

(high)

R/W

251Ah

Motor constant L, 2nd motor

H222 (low)

R/W

1 to 65530

0.01 [mH]

251Bh H223

(high)

R/W

251Ch

Motor constant Io, 2nd motor

H223 (low)

R/W

1 to 65530

0.01 [A]

251Dh H224

(high)

R/W

251Eh

Motor constant J, 2nd motor

H224 (low)

R/W

1 to 9999000

0.001

251Fh to

2523h

(Reserved) -

-

Inaccessible

-

2524h H230

(high)

R/W

2525h

Auto constant R1, 2nd motor

H230 (low)

R/W

1 to 65530

0.001 [Ω]

2526h H231

(high)

R/W

2527h

Auto constant R2, 2nd motor

H231 (low)

R/W

1 to 65530

0.001 [Ω]

2528h H232

(high)

R/W

2529h

Auto constant L, 2nd motor

H232 (low)

R/W

1 to 65530

0.01 [mH]

252Ah H233

(high)

R/W

252Bh

Auto constant Io, 2nd motor

H233 (low)

R/W

1 to 65530

0.01 [A]

252Ch H234

(high)

R/W

252Dh

Auto constant J, 2nd motor

H234 (low)

R/W

1 to 9999000

0.001

252Eh to

253Ch

(Reserved) -

-

Inaccessible

-

253Dh

PI proportional gain for 2nd
motor

H250

R/W 0 to 10000

0.1 [%]

253Eh

PI integral gain for 2nd motor

H251

R/W 0 to 10000

0.1 [%]

253Fh

P proportional gain setting for
2nd motor

H252

R/W 0 to 1000

0.01

2540h to

2546h

(Reserved) -

-

Inaccessible

-

2547h

Zero LV lmit for 2nd motor

H260

R/W 0 to 1000

0.1 [%]

2548h

Zero LV starting boost current
for 2nd motor

H261

R/W 0 to 50

1 [%]

2549h to

3102h

(Reserved) -

-

Inaccessible

-


*1 The following table lists the code data for parameter "H203" (motor capacity selection):

Code

data

00 01 02 03 04 05 06 07 08 09 10

Japan or U.S.A. mode

(b085 = 00 or 02)

0.2 kW

-

0.4

-

0.75

-

1.5

2.2

-

3.7

-

EU mode (b085 = 01)

0.2 kW 0.37

- 0.55

0.75

1.1 1.5 2.2 3.0 - 4.0

Code

data

11 12 13 14 15 16 17 18 19 20 21

Japan or U.S.A. mode

(b085 = 00 or 02)

5.5

kW

7.5 11 15 18.5 22 30 37 45 55 75

EU mode (b085 = 01)

5.5 kW 7.5

11

15

18.5

22

30

37

45

55

75

Advertising