Page

d025

User monitor 0

-2147483647 to 2147483647 (upper 4 digits including “-“)

d026

User monitor 1

-2147483647 to 2147483647 (upper 4 digits including “-“)

d027

User monitor 2

-2147483647 to 2147483647 (upper 4 digits including “-“)

4-5

d028

Pulse counter

0 to 2147483647 (upper 4 digits)

4-5

d029

Position setting monitor

-1073741823 to 1073741823 (upper 4 digits including “-“)

4-5

d030

Position feedback monitor

-1073741823 to 1073741823 (upper 4 digits including “-“)

4-5

d080

Trip Counter

0. to 9999., 1000 to 6553 (10000 to 65530) (times)

4-5

d081

Trip monitoring 1

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)

d082

Trip monitoring 2

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)

d083

Trip monitoring 3

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)

d084

Trip monitoring 4

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)

d085

Trip monitoring 5

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)

d086

Trip monitoring 6

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)

4-6

d090

Programming error monitoring

Warning code

4-6

d102

DC voltage monitoring

0.0 to 999.9 (V)

4-6

d103

BRD load factor monitoring

0.0 to 100.0 (%)

4-6

d104

Electronic thermal overload monitoring

0.0 to 100.0 (%)

4-6


8.3 Function Mode

Default

Code

Function name

Monitored data or setting

_FF

_FEF

_FUF

Setting during

operation

(allowed or

not)

Change during

operation

(allowed or

not)

Page

F001

Output frequency setting

0.0, "start frequency" to "maximum frequency" (or maximum frequency,
2nd/3rd motors) (Hz)
0.0 to 100.0 (when PID function is enabled)

0.00

{

{

4-7

F002

Acceleration (1) time setting

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

30.00

{

{

4-10

F202

Acceleration (1) time setting, 2nd
motor

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

30.00

{

{

4-10

F302

Acceleration (1) time setting, 3rd
motor

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

30.00

{

{

4-10

F003

Deceleration (1) time setting

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

30.00

{

{

4-10

F203

Deceleration time setting, 2nd motor

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

30.00

{

{

4-10

F303

Deceleration time setting, 3rd motor

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

30.00

{

{

4-10

F004

Keypad Run key routing

00 (forward rotation), 01 (reverse rotation)

00

¯

¯

4-7

Advertising