Chapter 8 list of data settings – Hitachi SJ700-2 User Manual

Page 268

Advertising
background image

Chapter 8 List of Data Settings

8 - 8

Default

Code

Function name

Monitored data or setting

_FF _FEF _FUF

Setting during

operation

(allowed or

not)

Change

during

operation

(allowed or

not)

Page

b078

Cumulative input power data
clearance

Clearance by setting "01" and pressing the STR key

00

{

{

b079

Cumulative input power display
gain setting

1. to 1000.

1.

{

{

4-4

b082

Start frequency adjustment

0.10 to 9.99 (Hz)

0.50

¯

{

4-42

b083

Carrier frequency setting

0.5 to 15.0 (kHz) (subject to derating)

5.0

¯

¯

4-43

b084

Initialization mode (parameters or
trip history)

00 (clearing the trip history), 01 (initializing the data),
02 (clearing the trip history and initializing the data)

00

¯

¯

b085

Country code for initialization

00 (Japan), 01 (EU), 02 (U.S.A.)

00

01

02

¯

¯

4-75

b086

Frequency scaling conversion
factor

0.1 to 99.0

1.0

{

{

4-2

b087

STOP key enable

00 (enabling), 01 (disabling), 02 (disabling only the function to stop)

00

¯

{

4-9

b088

Restart mode after FRS

00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (starting
with active matching frequency)

00

¯

{

4-52

b089

Automatic carrier frequency
reduction

00: invalid, 01: valid

00

¯

¯

4-44

b090

Dynamic braking usage ratio

0.0 to 100.0 (%)

0.0

¯

{

4-45

b091

Stop mode selection

00 (deceleration until stop), 01 (free-run stop)

00

¯

{

4-9

b092 Cooling

fan

control

00 (always operating the fan), 01 (operating the fan only during inverter
operation [including 5 minutes after power-on and power-off])

00

¯

{

b095

Dynamic braking control

00 (disabling), 01 (enabling [disabling while the motor is topped]), 02
(enabling [enabling also while the motor is topped])

00

¯

{

b096

Dynamic braking activation level

330 to 380, 660 to 760(V)

360/

720

¯

{

4-45

b098

Thermistor for thermal protection
control

00 (disabling the thermistor), 01 (enabling the thermistor with PTC), 02
(enabling the thermistor with NTC)

00

¯

{

Oth

e

rs

b099

Thermal protection level setting

0. to 9999. (

Ω)

3000.

¯

{

4-72

b100

Free-setting V/f frequency (1)

0. to "free-setting V/f frequency (2)" (Hz)

0.

¯

¯

b101

Free-setting V/f voltage (1)

0.0 to 800.0 (V)

0.0

¯

¯

b102

Free-setting V/f frequency (2)

0. to "free-setting V/f frequency (3)" (Hz)

0.

¯

¯

b103

Free-setting V/f voltage (2)

0.0 to 800.0 (V)

0.0

¯

¯

b104

Free-setting V/f frequency (3)

0. to "free-setting V/f frequency (4)" (Hz)

0.

¯

¯

b105

Free-setting V/f voltage (3)

0.0 to 800.0 (V)

0.0

¯

¯

b106

Free-setting V/f frequency (4)

0. to "free-setting V/f frequency (5)" (Hz)

0.

¯

¯

b107

Free-setting V/f voltage (4)

0.0 to 800.0 (V)

0.0

¯

¯

b108

Free-setting V/f frequency (5)

0. to "free-setting V/f frequency (6)" (Hz)

0.

¯

¯

b109

Free-setting V/f voltage (5)

0.0 to 800.0 (V)

0.0

¯

¯

b110

Free-setting V/f frequency (6)

0. to "free-setting V/f frequency (7)" (Hz)

0.

¯

¯

b111

Free-setting V/f voltage (6)

0.0 to 800.0 (V)

0.0

¯

¯

b112

Free-setting V/f frequency (7)

0. to "free-setting V/f frequency (8)" (Hz)

0.

¯

¯

F

re

e

se

tti

n

g

o

f V

/f ch

a

ra

c

te

ri

s

ti

c

b113

Free-setting V/f voltage (7)

0.0 to 800.0 (V)

0.0

¯

¯

4-17

b120

Brake Control Enable

00 (disabling), 01 (enabling)

00

¯

{

b121

Brake Wait Time for Release

0.00 to 5.00 (s)

0.00

¯

{

b122

Brake Wait Time for Acceleration

0.00 to 5.00 (s)

0.00

¯

{

b123

Brake Wait Time for Stopping

0.00 to 5.00 (s)

0.00

¯

{

b124

Brake Wait Time for Confirmation

0.00 to 5.00 (s)

0.00

¯

{

b125

Brake Release Frequency Setting 0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

¯

{

b126

Brake Release Current Setting

0.0 to 2.00 x "rated current"

Rated current of inverter

¯

{

b127

Braking frequency

0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

¯

{

4-81

b130

Overvoltage suppression enable

00 (disabling the restraint), 01 (controlled deceleration), 02 (enabling
acceleration)

00

¯

{

b131

Overvoltage suppression level

330 to 390 (V) (200 V class model), 660 to 780 (V) (400 V class model)

380/

760

¯

{

b132

Acceleration and deceleration
rate at overvoltage suppression

0.10 to 30.00 (s)

1.00

¯

{

b133

Overvoltage suppression
propotional gain

0.00 to 2.55

0.50

{

{

Oth

e

rs

b134

Overvoltage suppression Integral
time

0.000 to 9.999 / 10.00 to 65.53 (s)

0.060

{

{

4-41