Chapter 4 Explanation of Functions

Connection

As illustrated below, connect the inverters in parallel to the external control system, and connect the
RP and SN terminals with a jumper on the inverter at the end of the network. (Similarly jumper the RP
and SN terminals when only one inverter is connected to the external control system for RS485
communication.) Connecting the RP and SN terminals enables the terminating resistor in the control
circuit terminal block board of the inverter, which suppresses signal reflections.

External control

system












SP SN RP SN

SP SN RP SN

SP SN RP SN



(2) Required settings
The following table lists the inverter settings required for the RS485 communication:

Item

Function code

Data or range of data

Description

02 Loopback

test

03 2,400

bps

04 4,800

bps

05 9,600

bps

Communication speed
selection

C071

06 19,200

bps

Node allocation

C072

1. to 32.

Assignment of a station number to the
inverter
(Set this item when your inverter is
connected together with other(s) to a
control system.)

7 7

bits

Communication data length
selection

C073

8 8

bits

00 No

parity

01 Even

parity

Communication parity
selection

C074

02 Odd

parity

1 1

bit

Communication stop bit
selection

C075

2 2

bits

00 Tripping

01

Tripping after decelerating and stopping
the motor

02

Ignoring the errors

03

Stopping the motor after free-running

Selection of operation after
communication error

C076

04

Decelerating and stopping the motor

Communication trip limit time
setting

C077

0.00 to 99.99 (s)

Limit length of time to determine
communication train disconnection

Communication wait time

C078

0. to 1000. (ms)

Time to wait until the inverter returns a
response

00 ASCII

mode

Communication mode
selection

C079

01 Modbus-RTU

mode

4 - 11