Chapter 4 explanation of functions – Hitachi SJ700-2 User Manual

Page 131

Advertising
background image

Chapter 4 Explanation of Functions

4.2.69 Cooling-fan speed drop signal (WAF)

4 -

68

The inverter outputs the cooling-fan speed drop (WAF) signal
when it detects that the rotation speed of its internal cooling fan
has fallen to 75% or less of the full speed.
If "01" has been selected for the cooling fan control (b092), the
inverter will not output the WAF signal, even when the cooling fan
stops.

C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
b092: Cooling fan control
d022: Life-check monitoring

Related code

If the WAF signal is output, check the cooling-fan cover for clogging.
You can monitor the state of the WAF signal by using the life-check monitoring function (d022).

Item Function

code

Data

Description

Terminal function

C021 to C025

Alarm relay terminal function

C026

40

WAF: Cooling-fan speed
drop signal


4.2.70 Starting contact signal (FR)

If the forward operation (FW) and reverse operation (RV) commands are input at the same time, the
inverter stops the motor operation.

C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function

Related code

The inverter outputs the starting contact (FR) signal while it is
receiving an operation command.
The FR signal is output, regardless of the setting of the run command source setting (A002).

Item Function

code

Data

Description

Terminal function

C021 to C025

Alarm relay terminal function

C026

41

FR: Starting contact
signal


Forwa

St

rd operation command

Reverse operation command

arting contact signal (FR)








4.2.71 Heat sink overheat warning signal (OHF)

Description

C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
C064: Heat sink overheat warning level

Related code

The inverter monitors the temperature of its internal heat sink,
and outputs the heat sink overheat warning (OHF) signal when
the temperature exceeds the heat sink overheat warning level
(C064).

Item

Function code

Data or range of data

Terminal function

C021 to C025

Alarm relay terminal function

C026

42

OHF: Heat sink overheat warning
signal

Heat sink overheat warning level

Setting of the threshold
temperature at which to output the
heat sink overheat warning signal

C064

0. to 200. (℃)

Advertising