Chapter 5 error codes – Hitachi SJ700-2 User Manual

Page 239

Advertising
background image

Chapter 5 Error Codes

3) Error indications by protective functions with the DeviceNet option board (SJ-DN) mounted

5 - 7

OP1-9

OP2-9

OP1-2

OP2-2

OP1-0

OP2-0

Name Description

Display on

digital operator

Display on

remote operator

Troubleshooting and corrective action

Reference

page

DeviceNet

communicatio

n error

If the disconnection due to the Bus-Off
signal or timeout occurs during the
operation using DeviceNet commands,
the inverter will shut off its output and
display the error code shown on the right.
(The inverter will trip according to the
settings of "p45" and "P048".)

Check whether the communication speed
setting is correct.
Check whether the wiring distance is
appropriate.
Check the connections.

OP1-1

OP2-1

Duplicate

MAC ID

If two or more devices having the same
MAC ID are detected in the same
network, the inverter will display the error
code shown on the right.

Check whether duplicate MAC IDs are
used.

External trip

If the Force Fault/Trip bit of Attribute 17 in
the Instance 1 of the Control Supervisory
object is set to "1", the inverter will shut
off its output and display the error code
shown on the right.

Check whether the Attribute 17 in the
Instance 1 of Class 29 is "1". (If so, clear
the bit to "0".)

Inverter

communicatio

n error

If timeout occurs during the
communication between the inverter and
DeviceNet option board, the inverter will
shut off its output and display the error
code shown on the right.

Check whether the option board has been
disconnected from the inverter.

Refer to the

instruction

manual for

the SJ-DN.

Note: If the option board does not operate normally, confirm the DIP switch settings on the option board.

Functions of the DIP switches on the DeviceNet option board (SJ-DN)

Setting of DeviceNet baud rate (DIP switches No. 1 and No. 2)

Baud rate

125 kbps

250 kbps

500 kbps

DIP switch setting

Setting of MAC ID (DIP switches No. 3 to No. 8)

MAC ID

Dip switch setting

The left-most switch indicates the highest-order bit of MAC ID. Therefore, the
example of switch settings shown on the left indicates the following MAC ID:

= 29 (hexadecimal) = 41 (decimal)

ON

OFF

DR1 DRO

DR

ON

OFF

DR1 DRO

DR

ON

OFF

DR1 DRO

DR

Note: For details, refer to the instruction manual for the option board.