Chapter 4 Explanation of Functions

4 -

71

4.2.77 Window comparators (WCO/WCOI/WCO2) (detection of terminal disconnection:
ODc/OIDc/O2Dc)

- The window comparator function outputs
signals when the values of analog inputs O,
OI, and O2 are within the maximum and
minimum limits specified for the window comparator. You can monitor analog inputs with reference to
arbitrary levels (to find input terminal disconnection and other errors).
- You can specify a hysteresis width for the maximum-limit and minimum-limit levels of the window
comparator.
- You can specify limit levels and a hysteresis width individually for analog inputs O, OI, and O2.
- You can fix the analog input data to be applied to an arbitrary value when WCO, WCOI, or WCO2 is
output. For this purpose, specify a desired value as the operation level at O/OI/O2 disconnection
(b070/b071/b072). When "no" is specified, the analog input data is reflected as input.

C021 to C025: Terminal [11] to terminal [15] functions
C026: Alarm relay terminal function
b060/b063/b066: Maximum-limit level of window comparators O/OI/O2
b061/b064/b067: Minimum-limit level of window comparators O/OI/O2

Related code

- Output values of ODc, OIDc, and O2Dc are the same as those of WCO, WCOI, and WCO2, respectively.

Item

Function

code

Range of data

Description

27

ODc: Detection of analog input O
disconnection

28

OIDc: Detection of analog input OI
disconnection

Terminal [11] to terminal
[15] functions

29

O2Dc: Detection of analog input O2
disconnection

54

WCO: Window comparator O

55

WCOI: Window comparator OI

Alarm relay terminal
function

C021-C025

C026

56

WCO2: Window comparator O2

b060 (O )
b063 (OI)

"Minimum-limit level + hysteresis width/2

(minimum of 0)" to 100. (%)

Maximum-limit level of
window comparators
O/OI/O2

b066 (O2)

"Minimum-limit level + hysteresis width/2

(minimum of -100)" to 100. (%)

Setting of maximum-limit level

b061 (O )
b064 (OI)

0 to "maximum-limit level - hysteresis

width/2 (maximum of 100)" (%)

Minimum-limit level of
window comparators
O/OI/O2

b067 (O2)

-100 to "maximum-limit level - hysteresis

width/2 (maximum of 100)" (%)

Setting of minimum-limit level

b062 (O )
b065 (OI)

Hysteresis width of
window comparators
O/OI/O2

b068 (O2)

0 to "(maximum-limit level - minimum-limit

level)/2 (maximum of 10)" (%)

Setting of hysteresis width for
maximum-limit and minimum-limit
levels

b070 (O )

b071 (OI)

0 to 100 (%) or "no" (ignore)

Operation level at
O/OI/O2 disconnection

b072 (O2)

-100 to 100 (%) or "no" (ignore)

Setting of the analog input value to be
applied when WCO, WCOI, or WCO2
(ODc, OIDc, or O2Dc) is output.

Maximum-limit level of window
comparator (b061/b064/b067)

Minimum-limit level of window
comparator (b060/b063/b066)

WCO/WCOI/WCO2
ODc/OIDc/O2Dc

Max(100%)

Min(O/OI:0%)
(O2 :-100%)

O, OI, or O2

Applied analog data

Applied analog data

Analog operation level at
disconnection (b070/b071/b072)

Hysteresis width

(b062,b065,b068)