Chapter 8 List of Data Settings

8 - 10

Default

Code

Function name

Monitored data or setting

_FF _FEF

_FUF

Setting

during

operation

(allowed

or not)

Change

during

operation

(allowed

or not)

Page

C021

Terminal [11] function

01

¯

{

C022

Terminal [12] function

00

¯

{

C023

Terminal [13] function

03

¯

{

C024

Terminal [14] function

07

¯

{

C025

Terminal [15] function

40

¯

{

In

te

lligent

ou

tput t

e

rm

inals

C026

Alarm relay terminal function

00 (RUN: running), 01 (FA1: constant-speed reached), 02 (FA2: set
frequency overreached), 03 (OL: overload notice advance signal (1)), 04
(OD: output deviation for PID control), 05 (AL: alarm signal), 06 (FA3: set
frequency reached), 07 (OTQ: over-torque), 08 (IP: instantaneous power
failure), 09 (UV: undervoltage), 10 (TRQ: torque limited), 11 (RNT:
operation time over), 12 (ONT: plug-in time over), 13 (THM: thermal alarm
signal), 19 (BRK: brake release), 20 (BER: braking error), 21 (ZS: 0 Hz
detection signal), 22 (DSE: speed deviation maximum), 23 (POK:
positioning completed), 24 (FA4: set frequency overreached 2), 25 (FA5:
set frequency reached 2), 26 (OL2: overload notice advance signal (2)), 27
(Odc: Analog O disconnection detection), 28 (OIDc: Analog OI
disconnection detection), 29 (O2Dc: Analog O2 disconnection detection),
31 (FBV: PID feedback comparison), 32 (NDc: communication line
disconnection), 33 (LOG1: logical operation result 1), 34 (LOG2: logical
operation result 2), 35 (LOG3: logical operation result 3), 36 (LOG4: logical
operation result 4), 37 (LOG5: logical operation result 5), 38 (LOG6: logical
operation result 6), 39 (WAC: capacitor life warning), 40 (WAF: cooling-fan
speed drop), 41 (FR: starting contact signal), 42 (OHF: heat sink overheat
warning), 43 (LOC: low-current indication signal), 44 (M01:
general-purpose output 1), 45 (M02: general-purpose output 2), 46 (M03:
general-purpose output 3), 47 (M04: general-purpose output 4), 48 (M05:
general-purpose output 5), 49 (M06: general-purpose output 6), 50 (IRDY:
inverter ready), 51 (FWR: forward rotation), 52 (RVR: reverse rotation), 53
(MJA: major failure), 54(WCO: window comparator O), 55(WCOI: window
comparator OI), 56 (WCO2: window comparator O2)
(When alarm code output is selected for "C062", functions "AC0" to "AC2"
or "AC0" to "AC3" [ACn: alarm code output] are forcibly assigned to
intelligent output terminals 11 to 13 or 11 to 14, respectively.)

05

¯

{

4-60

C027

[FM] siginal selection

00 (output frequency), 01 (output current), 02 (output torque), 03 (digital
output frequency), 04 (output voltage), 05 (input power), 06 (electronic
thermal overload), 07 (LAD frequency), 08 (digital current monitoring), 09
(motor temperature), 10 (heat sink temperature), 12 (general-purpose
output YA0)

00

¯

{

4-73

C028

[AM] siginal selection

00 (output frequency), 01 (output current), 02 (output torque), 04 (output
voltage), 05 (input power), 06 (electronic thermal overload), 07 (LAD
frequency), 09 (motor temperature), 10 (heat sink temperature), 11 (output
torque [signed value]), 13 (general-purpose output YA1)

00

¯

{

C029

[AMI] siginal selection

00 (output frequency), 01 (output current), 02 (output torque), 04 (output
voltage), 05 (input power), 06 (electronic thermal overload), 07 (LAD
frequency), 09 (motor temperature), 10 (heat sink temperature), 14
(general-purpose output YA2)

00

¯

{

4-74

Analog m

onit

o

ri

ng

C030

Digital current monitor reference
value

0.20 x "rated current" to 2.00 x "rated current" (A)
(Current with digital current monitor output at 1,440 Hz)

Rated current of inverter

{

{

4-73

C031

Terminal [11] active state

00 (NO) / 01 (NC)

00

¯

{

C032

Terminal [12] active state

00 (NO) / 01 (NC)

00

¯

{

C033

Terminal [13] active state

00 (NO) / 01 (NC)

00

¯

{

C034

Terminal [14] active state

00 (NO) / 01 (NC)

00

¯

{

C035

Terminal [15] active state

00 (NO) / 01 (NC)

00

¯

{

In

te

lligent

ou

tput

ter

m

inals

C036

Alarm relay active state

00 (NO) / 01 (NC)

01

¯

{

4-61