Chapter 4 Explanation of Functions

4 - 154

Register

No.

Function name

Function

code

R/W

Monitoring and setting items Data resolution

Register

No.

1326h

Reduced voltage start selection

b036

R/W

0 (minimum reduced voltage start time) to 255
(maximum reduced voltage start time)

-

1327h

Function code display restriction

b037

R/W

0 (full display), 1 (function-specific display), 2 (user
setting), 3 (data comparison display), 4
(basicdisplay)

-

1328h Initial-screen

selection

b038

R/W

0 (screen displayed when the STR key was pressed
last), 1 (d001), 2 (d002), 3 (d003), 4 (d007), 5 (F001)

-

1329h

Automatic user-parameter
setting function enable

b039

R/W 0 (disabling), 1 (enabling)

-

132Ah

Torque limit selection

b040

R/W

00 (quadrant-specific setting), 01 (switching by
terminal), 02 (analog input), 03 (option 1),
04 (option 2)

-

132Bh

Torque limit (1) (forward-driving
in 4-quadrant mode)

b041

R/W 0 to 200/255 (no)

1 [%]

132Ch

Torque limit (2) (reverse-
regenerating in 4-quadrant
mode)

b042

R/W 0 to 200/255 (no)

1 [%]

132Dh

Torque limit (3) (reverse-driving
in 4-quadrant mode)

b043

R/W 0 to 200/255 (no)

1 [%]

132Eh

Torque limit (4) (forward-
regenerating in 4-quadrant
mode)

b044

R/W 0 to 200/255 (no)

1 [%]

132Fh

Torque limit LADSTOP enable

b045

R/W 0 (disabling), 1 (enabling)

-

1330h

Reverse Run protection enable

b046

R/W 0 (disabling), 1 (enabling)

-

1331h to

1333h

(Reserved) -

-

Inaccessible

-

1334h

Controller deceleration and stop
on power loss

b050 R/W

0 (disabling), 1 (enabling), 2, (nonstop operation at
momentary power failure (no restoration))
3, (nonstop operation at momentary power failure
(restoration to be done))

-

1335h

DC bus voltage trigger level
during power loss

b051

R/W 0 to 10000

0.1 [V]

1336h

Over-voltage threshold during
power loss

b052

R/W 0 to 10000

0.1 [V]

1337h b053

(high)

R/W

1338h

Deceleration time setting during
power loss (target voltage level)

b053 (low)

R/W

0 to 360000

0.01

[sec.]

1339h

Initial output frequency decrease
during power loss

b054

R/W 0 to 1000

0.01 [Hz]

133Ah

Proportional gain setting for
nonstop operation at momentary
power failure

b055

R/W 0 to 255

0.01

133Bh

Integral time setting for nonstop
operation at momentary power
failure

b056

R/W 0 to 65535

0.001

[sec]

133Ch to

133Eh

(Reserved) -

-

Inaccessible

-

133Fh

Maximum-limit level of window
comparators O

b060 R/W

1340h

Minimum-limit level of window
comparators O

b061 R/W

1341h

Hysteresis width of window
comparators O

b062 R/W

1342h

Maximum-limit level of window
comparators OI

b063 R/W

1343h

Minimum-limit level of window
comparators OI

b064 R/W

1344h

Hysteresis width of window
comparators OI

b065 R/W

1345h

Maximum-limit level of window
comparators OI

b066 R/W

1346h

Minimum-limit level of window
comparators O/OI/O2

b067 R/W

1347h

Hysteresis width of window
comparators O/OI/O2

b068 R/W

1348h (Reserved)

-

- Inaccessible

-

1349h

Operation level at O
disconnection

b070 R/W

134Ah

Operation level at OI
disconnection

b071 R/W

134Bh

Operation level at O2
disconnection

b072 R/W

134Ch to

1350

(reserved) -

-

Inaccessible

1351h

Cumulative input power data
clearance

b060

R/W Clearance by setting "1"

-