Chapter 4 explanation of functions, 4 - 147 (iii) list of registers (monitoring), Iv) list of registers – Hitachi SJ700-2 User Manual

Page 210

Advertising
background image

Chapter 4 Explanation of Functions

4 - 147

(iii) List of registers (monitoring)

Register

No.

Function name

Function code

R/W

Monitoring and setting items

Data

resolution

1001h d001

(high)

1002h

Output frequency monitoring

d001 (low)

R

0 to 40000

0.01 [Hz]

1003h

Output current monitoring

d002

R

0 to 9999

0.1 [A]

1004h

Rotation direction minitoring

d003

R

0: Stopping, 1: Forward rotation, 2: Reverse
rotation

0.1 [Hz]

1005h d004

(high)

1006h

Process variable (PV), PID
feedback monitoring

d004 (low)

R

0 to 9990

0.1

1007h

Intelligent input terminal status

d005

R

2^0: Terminal 1 to 2^7: Terminal 8

1 bit

1008h

Intelligent output terminal
status

d006

R

2^0: Terminal 11 to 2^4: Terminal 15

1 bit

1009h d007

(high)

100Ah

Scaled output frequency
monitoring

d007 (low)

R

0 to 39960

0.01

100Bh d008

(high)

R

100Ch

Actual-frequency monitoring

d008 (low)

R

-40000 to +40000

0.01 [Hz]

100Dh

Torque command monitoring

d009

R

-200 to +200

1 [%]

100Eh

Torque bias monitoring

d010

R

-200 to +200

1 [%]

100Fh (Reserved)

-

- Inaccessible

-

1010h

Torque monitoring

d012

R

-200 to +200

1 [%]

1011h

Output voltage monitoring

d013

R

0 to 6000

0.1 [V]

1012h

Power monitoring

d014

R

0 to 9999

0.1 [kW]

1013h d015

(high)

1014h

Cumulative power monitoring

d015 (low)

R

0 to 9999999

0.1

1015h d016

(high)

1016h

Cumulative operation RUN
time monitoring

d016 (low)

R

0 to 999900

0.1

1017h d017

(high)

1018h

Cumulative power-on time
monitoring

d017 (low)

R

0 to 999900

1 [h]

1019h

Heat sink temperature
monitoring

d018

R

-200 to 2000

0.1 [℃]

101Ah

Motor temperature monitoring

d019

R

-200 to 2000

0.1 [℃]

101Bh

101Ch

(Reserved) -

-

Inaccessible

-

101Dh Life-check

monitoring

d022

R

2^0: Capacitor on main circuit board
2^1: Low cooling-fan speed

1 bit

101Eh to

1025h

(Reserved) -

-

Inaccessible

-

1026h

DC voltage monitoring (across
P and N)

d102

R

0 to 9999

0.1 [V]

1027h

BRD load factor monitoring

d103

R

0 to 1000

0.1 [%]

1028h

Electronic thermal overload
monitoring

d104

R

0 to 1000

0.1 [%]

1029h to

102Dh

(reserved) -

-

Inaccessible

-

102Eh d025(HIGH)

R

102Fh

User monitor 1

d025(LOW) R

-2147483647 to 2147483647

1

1030h d026(HIGH)

R

1031h

User monitor 1

d026(LOW) R

-2147483647 to 2147483647

1

1032h d027(HIGH)

R

1033h

User monitor 1

d027(LOW) R

-2147483647 to 2147483647

1

1034h d028(HIGH)

R/W

1035h

Pulse counter

d028(LOW) R/W

0 to 2147483647

1

1036h d029(HIGH)

R

1037h

Position setting monitor

d029(LOW) R

-2147483647 to 2147483647

1

1038h d030(HIGH)

R

1039h

Position feedback monitor

d030(LOW) R

-2147483647 to 2147483647

1

103Ah to

1102h

Unused -

Inaccessible

-


(iv) List of registers

Register

No.

Function name

Function code

R/W

Monitoring and setting items

Data

resolution

1103h F002

(high)

1104h

Acceleration (1) time setting

F002 (low)

R/W 1 to 360000

0.01 [sec.]

1105h F003

(high)

1106h

Deceleration (1) time setting

F003 (low)

R/W 1 to 360000

0.01 [sec.]

1107h

Keypad Run key routing

F004

R/W 0 (forward rotation), 1 (reverse rotation)

-

1108h to

1200h

Unused -

-

Inaccessible

-

Advertising