Chapter 4 explanation of functions – Hitachi SJ700-2 User Manual

Page 222

Advertising
background image

Chapter 4 Explanation of Functions

4 - 159

Register

No.

Function name

Function code

R/W

Monitoring and setting items Data resolution

Register

No.

142Ah C042

(high)

R/W

142Bh

Frequency arrival setting for accel.

C042 (low)

R/W

0 to 40000

0.01 [Hz]

142Ch C043

(high)

R/W

142Dh

Frequency arrival setting for decel.

C043 (low)

R/W

0 to 40000

0.01 [Hz]

142Eh PID deviation level setting

C044

R/W 0 to 1000

0.1 [%]

142Fh C045

(high)

R/W

1430h

Frequency arrival setting for
acceleration (2)

C045 (low)

R/W

0 to 40000

0.01 [Hz]

1431h C046

(high)

R/W

1432h

Frequency arrival setting for
deceleration (2)

C046 (low)

R/W

0 to 40000

0.01 [Hz]

1433h to

1437h

(Reserved) -

-

Inaccessible

-

1438h Maximum PID feedback data

C052

R/W 0 to 1000

0.1 [%]

1439h Minimum PID feedback data

C053

R/W 0 to 1000

0.1 [%]

143Ah (Reserved)

R/W

-

143Bh

Over-torque (forward-driving) level
setting

C055

R/W 0 to 200

1 [%]

143Ch

Over-torque (reverse regenerating)
level setting

C056

R/W 0 to 200

1 [%]

143Dh

Over-torque (reverse driving) level
setting

C057

R/W 0 to 200

1 [%]

143Eh

Over-torque (forward regenerating)
level setting

C058

R/W 0 to 200

1 [%]

143Fh (Reserved)

-

- Inaccessible

-

1440h (Reserved)

-

- Inaccessible

-

1441h

Electronic thermal warning level
setting

C061

R/W 0 to 100

1 [%]

1442h Alarm code output

C062

R/W 0 (disabling alarm output), 1 (3 bits), 2 (4 bits)

-

1443h Zero speed detection level

C063

R/W 0 to 10000

0.01 [Hz]

1444h Heat sink overheat warning level

C064

R/W 0 to 200

1 [℃]

1445h to

144Ah

(Reserved) -

-

Inaccessible

-

144Bh Communication speed selection

C071

R/W

2 (loopback test), 3 (2,400 bps), 4 (4,800 bps), 5
(9,600 bps), 6 (19,200 bps)

-

144Ch Node allocation

C072

R/W 1. to 32.

-

144Dh

Communication data length
selection

C073

R/W 7 (7 bits), 8 (8 bits)

-

144Eh Communication parity selection

C074

R/W 00 (no parity), 01 (even parity), 02 (odd parity)

-

144Fh Communication stop bit selection

C075

R/W 1 (1 bit), 2 (2 bits)

-

1450h

Selection of the operation after
communication error

C076 R/W

0 (tripping), 1 (tripping after decelerating and
stopping the motor), 2 (ignoring errors), 3
(stopping the motor after free-running), 4
(decelerating and stopping the motor)

-

1451h Communication timeout limit

C077

R/W 0 to 9999

0.01 [sec.]

1452h Communication wait time

C078

R/W 0 to 1000

1 [msec.]

1453h Communication mode selection

C079

R/W 0 (ASCII), 1 (Modbus-RTU)

-

1454h (Reserved)

-

- Inaccessible

-

1455h [O] input span calibration

C081

R/W 0 to 65530

1

1456h [OI] input span calibration

C082

R/W 0 to 65530

1

1457h [O2] input span calibration

C083

R/W 0 to 65530

1

1458h (Reserved)

-

- Inaccessible

-

1459h Thermistor input tuning

C085

R/W 0 to 10000

0.1

145Ah to

145Eh

(Reserved) -

-

Inaccessible

-

145Fh Debug

mode

enable

C091

R 0/1

-

1460h to

1468h

(Reserved) -

-

Inaccessible

-

1469h Up/Down memory mode selection

C101

R/W

0 (not storing the frequency data), 1 (storing the
frequency data)

-

146Ah Reset mode selection

C102

R/W

0 (resetting the trip when RS is on), 1 (resetting
the trip when RS is off), 2 (enabling resetting
only upon tripping [resetting when RS is on])

-

146Bh Restart mode after reset

C103

R/W

0 (starting with 0 Hz), 1 (starting with matching
frequency), 2 (restarting with active matching
frequency)

-

146Ch (Reserved)

-

- Inaccessible

-

146Dh FM gain adjustment

C105

R/W 50 to 200

1 [%]

146Eh AM gain adjustment

C106

R/W 50 to 200

1 [%]

146Fh AMI gain adjustment

C107

R/W 50 to 200

1 [%]