Chapter 4 Explanation of Functions

The commands are described below.
(i) 00 command: This command instructs the inverter to drive the motor (for forward or reverse rotation)

or stop the motor. (To use this command, set "A002" to "03" [RS485].)

- Transmission frame
Frame format

STX Station

No.

Command Data

BCC

CR

Description

Data

size

Setting

STX

Control code (Start of TeXt)

1 byte

STX (0x02)

Station No.

Station number of control-target
inverter

2 bytes

01 to 32, or FF (broadcast to all stations)

Command

Command to be transmitted

2 bytes

00

Data

Data to be transmitted

1 byte

See Note 1.

BCC

Block check code

2 bytes

XOR of the items from "Station No." to "Data."
See Item (3) of this section.

CR

Control code (Carriage Return)

1 byte

CR (0x0D)

Note 1:

Data Description

Remarks

0 Stop

command

1

Forward rotation command

2

Reverse rotation command


(Example) When sending a forward rotation command to the inverter with station No. 01:
(STX) |01|00|1| (BCC) | (CR) 02|30 31|30 30|31|33 30|0D

Conversion into ASCII format

- Response frame
Positive response: See Item (2)-(i) of this section.
Negative response: See Item (2)-(ii) of this section.

(ii) 01 command: This command sets the inverter output frequency. (To use this command, set "A001" to

"03" [RS485].)

- Transmission frame
Frame format

STX Station

No.

Command Data

BCC

CR

Description

Data

size

Setting

STX

Control code (Start of TeXt)

1 byte

STX (0x02)

Station No.

Station number of control-target
inverter

2 bytes

01 to 32, or FF (broadcast to all stations)

Command

Command to be transmitted

2 bytes

01

Data

Data to be sent (decimal ASCII
code)

6 bytes

See Note 2.

BCC

Block check code

2 bytes

XOR of the items from "Station No." to "Data."
See Item (3) of this section.

CR

Control code (Carriage Return)

1 byte

CR (0x0D)

Note 2: For example, to set the output frequency of the inverter with station No. 01 to 5 Hz, the data is as

follows:

(STX) |01|01|000500| (BCC) | (CR) 02|30 31|30 31|30 30 30 35 30 30|30 35|0D

Conversion into ASCII format

Note 3: The data indicates a value 100 times as large as the actual frequency value to be set.

(Example) 5 (Hz)

→ 500 → 000500 30 30 30 35 30 30

Conversion into ASCII format

Note 4: When using the data as the feedback data for PID control, set the most-significant byte to "1".

(Example) 5 (%)

→ 500 → 100500 31 30 30 35 30 30

Conversion into ASCII format

- Response frame
Positive response: See Item (2)-(i) of this section.
Negative response: See Item (2)-(ii) of this section.

4 - 12