Chapter 8 list of data settings – Hitachi SJ700-2 User Manual

Page 272

Advertising
background image

Chapter 8 List of Data Settings

8 - 12

Default

Code

Function name

Monitored data or setting

_FF _FEF

_FUF

Setting

during

operation

(allowed

or not)

Change

during

operation

(allowed

or not)

Page

Te

r

mi

nal

C111

Overload setting (2)

0.0 to 2.00 x "rated current" (A)

Rated current of inverter

{

{

4-40

C121

[O] input zero calibration

0. to 9999., 1000 to 6553 (10000 to 65530)

Factory setting

{

{

C122

[OI] input zero calibration

0. to 9999., 1000 to 6553 (10000 to 65530)

Factory setting

{

{

Adjust

m

ent

C123

[O2] input zero calibration

0. to 9999., 1000 to 6553 (10000 to 65530)

Factory setting

{

{

-

C130

Output 11 on-delay time

0.0 to 100.0 (s)

0.0

¯

{

C131

Output 11 off-delay time

0.0 to 100.0 (s)

0.0

¯

{

C132

Output 12 on-delay time

0.0 to 100.0 (s)

0.0

¯

{

C133

Output 12 off-delay time

0.0 to 100.0 (s)

0.0

¯

{

C134

Output 13 on-delay time

0.0 to 100.0 (s)

0.0

¯

{

C135

Output 13 off-delay time

0.0 to 100.0 (s)

0.0

¯

{

C136

Output 14 on-delay time

0.0 to 100.0 (s)

0.0

¯

{

C137

Output 14 off-delay time

0.0 to 100.0 (s)

0.0

¯

{

C138

Output 15 on-delay time

0.0 to 100.0 (s)

0.0

¯

{

C139

Output 15 off-delay time

0.0 to 100.0 (s)

0.0

¯

{

C140

Output RY on-delay time

0.0 to 100.0 (s)

0.0

¯

{

C141

Output RY off-delay time

0.0 to 100.0 (s)

0.0

¯

{

C142

Logical output signal 1 selection 1

Same as the settings of C021 to C026 (except those of LOG1 to LOG6)

00

¯

{

C143

Logical output signal 1 selection 2

Same as the settings of C021 to C026 (except those of LOG1 to LOG6)

00

¯

{

4-72

C144

Logical output signal 1 operator
selection

00 (AND), 01 (OR), 02 (XOR)

00

¯

{

C145

Logical output signal 2 selection 1

Same as the settings of C021 to C026 (except those of LOG1 to LOG6)

00

¯

{

C146

Logical output signal 2 selection 2

Same as the settings of C021 to C026 (except those of LOG1 to LOG6)

00

¯

{

C147

Logical output signal 2 operator
selection

00 (AND), 01 (OR), 02 (XOR)

00

¯

{

C148

Logical output signal 3 selection 1

Same as the settings of C021 to C026 (except those of LOG1 to LOG6)

00

¯

{

C149

Logical output signal 3 selection 2

Same as the settings of C021 to C026 (except those of LOG1 to LOG6)

00

¯

{

C150

Logical output signal 3 operator
selection

00 (AND), 01 (OR), 02 (XOR)

00

¯

{

C151

Logical output signal 4 selection 1

Same as the settings of C021 to C026 (except those of LOG1 to LOG6)

00

¯

{

C152

Logical output signal 4 selection 2

Same as the settings of C021 to C026 (except those of LOG1 to LOG6)

00

¯

{

C153

Logical output signal 4 operator
selection

00 (AND), 01 (OR), 02 (XOR)

00

¯

{

C154

Logical output signal 5 selection 1

Same as the settings of C021 to C026 (except those of LOG1 to LOG6)

00

¯

{

C155

Logical output signal 5 selection 2

Same as the settings of C021 to C026 (except those of LOG1 to LOG6)

00

¯

{

C156

Logical output signal 5 operator
selection

00 (AND), 01 (OR), 02 (XOR)

00

¯

{

C157

Logical output signal 6 selection 1

Same as the settings of C021 to C026 (except those of LOG1 to LOG6)

00

¯

{

C158

Logical output signal 6 selection 2

Same as the settings of C021 to C026 (except those of LOG1 to LOG6)

00

¯

{

O

u

tp

u

t

te

rm

inal oper

a

tio

n f

unc

ti

on

C159

Logical output signal 6 operator
selection

00 (AND), 01 (OR), 02 (XOR)

00

¯

{

4-66

C160

Input terminal response time
setting 1

0. to 200. (

¯2ms) 1

¯

{

C161

Input terminal response time
setting 2

0. to 200. (

¯2ms) 1

¯

{

C162

Input terminal response time
setting 3

0. to 200. (

¯2ms) 1

¯

{

C163

Input terminal response time
setting 4

0. to 200. (

¯2ms) 1

¯

{

C164

Input terminal response time
setting 5

0. to 200. (

¯2ms) 1

¯

{

C165

Input terminal response time
setting 6

0. to 200. (

¯2ms) 1

¯

{

C166

Input terminal response time
setting 7

0. to 200. (

¯2ms) 1

¯

{

C167

Input terminal response time
setting 8

0. to 200. (

¯2ms) 1

¯

{

Input t

e

rm

inal

response

C168

Input terminal response time
setting FW

0. to 200. (

¯2ms) 1

¯

{

4-72

Oth

e

r

C169

Multistage speed/position
determination time

0. to 200. (

¯10ms) 0

¯

{

4-48

4-108