Chapter 8 list of data settings – Hitachi SJ700-2 User Manual

Page 271

Advertising
background image

Chapter 8 List of Data Settings

8 - 11

Default

Code

Function name

Monitored data or setting

_FF _FEF

_FUF

Setting

during

operation

(allowed

or not)

Change

during

operation

(allowed

or not)

Page

C038

Low-current indication signal
output mode selection

00 (output during acceleration/deceleration and constant-speed operation),
01 (output only during constant-speed operation)

01

¯

{

C039

Low-current indication signal
detection level

0.0 to 2.00 x "rated current" (A)

Rated current of inverter

{

{

4-69

C040

Overload signal output mode

00 (output during acceleration/deceleration and constant-speed operation),
01 (output only during constant-speed operation)

01

¯

{

C041

Overload level setting

0.0 to 2.00 x "rated current" (A)

Rated current of inverter

{

{

4-40

C042

Frequency arrival setting for accel. 0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

¯

{

C043

Frequency arrival setting for decel. 0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

¯

{

4-62

C044

PID deviation level setting

0.0 to 100.0 (%)

3.0

¯

{

4-29

C045

Frequency arrival setting for
acceleration (2)

0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

¯

{

C046

Frequency arrival setting for
deceleration (2)

0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

¯

{

4-62

C052

Maximum PID feedback data

0.0 to 100.0 (%)

100.0

¯

{

C053

Minimum PID feedback data

0.0 to 100.0 (%)

0.0

¯

{

4-29

C055

Over-torque (forward-driving) level
setting

0. to 200. (%)

100.

¯

{

C056

Over-torque (reverse
regenerating) level setting

0. to 200. (%)

100.

¯

{

C057

Over-torque (reverse driving) level
setting

0. to 200. (%)

100.

¯

{

C058

Over-torque (forward
regenerating) level setting

0. to 200. (%)

100.

¯

{

4-65

C061

Electronic thermal warning level
setting

0. to 100. (%)

80.

¯

{

4-38

C062

Alarm code output

00 (disabling), 01 (3 bits), 02 (4 bits)

00

¯

{

4-65

C063

Zero speed detection level

0.00 to 99.99, 100.0 (Hz)

0.00

¯

{

4-64

Levels and ou

tput t

e

rm

inal sta

tus

C064

Heat sink overheat warning level

0. to 200.0 (

°C)

120.

¯

{

4-68

C071

Communication speed selection

02 (loopback test), 03 (2,400 bps), 04 (4,800 bps), 05 (9,600 bps), 06
(19,200 bps)

04

¯

{

C072

Node allocation

1. to 32.

1.

¯

{

C073

Communication data length
selection

7 (7 bits), 8 (8 bits)

7

¯

{

C074

Communication parity selection

00 (no parity), 01 (even parity), 02 (odd parity)

00

¯

{

C075

Communication stop bit selection

1 (1 bit), 2 (2 bits)

1

¯

{

C076

Selection of the operation after
communication error

00 (tripping), 01 (tripping after decelerating and stopping the motor), 02
(ignoring errors), 03 (stopping the motor after free-running), 04
(decelerating and stopping the motor)

02

¯

{

C077

Communication timeout limit
before tripping

0.00 to 99.99 (s)

0.00

¯

{

C078

Communication wait time

0. to 1000. (ms)

0.

¯

{

Com

m

unica

ti

on f

unc

ti

on

C079

Communication mode selection

00(ASCII), 01(Modbus-RTU)

00

¯

{

4-113

C081

[O] input span calibration

0. to 9999., 1000 to 6553(10000 to 65530)

Factory setting

{

{

C082

[OI] input span calibration

0. to 9999., 1000 to 6553(10000 to 65530)

Factory setting

{

{

C083

[O2] input span calibration

0. to 9999., 1000 to 6553(10000 to 65530)

Factory setting

{

{

C085

Thermistor input tuning

0.0 to 999.9, 1000.

Factory setting

{

{

4-72

Adjust

m

ent

C091

Debug mode enable

(Do not change this parameter, which is intended for factory adjustment.)

00

¯

¯

C101

Up/Down memory mode selection

00 (not storing the frequency data), 01 (storing the frequency data)

00

¯

{

4-56

C102 Reset

mode

selection

00 (resetting the trip when RS is on), 01 (resetting the trip when RS is off), 2
(enabling resetting only upon tripping [resetting when RS is on])

00

{

{

Oth

e

rs

C103

Restart mode after reset

00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (restarting
with active matching frequency)

00

¯

{

4-54

C105

FM gain adjustment

50. to 200. (%)

100.

{

{

4-73

C106

AM gain adjustment

50. to 200. (%)

100.

{

{

C107

AMI gain adjustment

50. to 200. (%)

100.

{

{

C109

AM bias adjustment

0. to 100. (%)

0.

{

{

Me

te

r

adjust

m

en

t

C110

AMI bias adjustment

0. to 100. (%)

20.

{

{

4-74

Advertising