Chapter 3 Operation

3.3 How To Make a Test Run

This section describes how to make a test run of the inverter that is wired and connected to external
devices in a general way as shown below.
For the detailed method of using the digital operator, see Section 3.2, "How To Operate the Digital
Operator."
(1) When entering operation and frequency-setting commands from the digital operator:

(The operating procedure below is common to the standard and optional digital operators.)

3 - 11


(Operating procedure)
1) Confirm that all wirings are correct.

Default jumper position for sinking type inputs
(Altanatively, CM1-PLC for souricing tiype)

3-phase
power supply

P24

PLC

CM1

TH

FM

1

8

. .

FW

R
S
T

AMI
L

AM

O2

OI

O

H

R
S
T

ELB

G

Type-D grounding (200 V class model)
Type-C grounding (400 V class model)

DC reactor

Motor

Alarm output contacts

Braking unit

Digital operator

SN

RP

CM2

SP
SN

PD

P

RB

N

AL0
AL1
AL2

11

15

. .

V
W

U

2) Turn on the earth-leakage breaker (ELB) to supply power to the inverter.

(The POWER lamp [red LED] of the digital operator goes on.)
*

When using an inverter with the factory setting, proceed to step 5).

3) Select the digital operator as the operating device via the frequency source setting function.

- Display the function code "A001" on the monitor screen, and then press the key once.

FUNC

(The monitor shows a 2-digit numeric value.)
- Use the and/or key to change the displayed numeric value to [02], and then press the

key once to specify the digital operator as the operating device to input frequency-setting
commands.

1

2

STR

(The display reverts to [A001].)

4) Select the digital operator as the operating device by the run command source setting function.

- Display the function code "A002" on the monitor screen, and then press the key once.

FUNC

(The monitor shows a 2-digit numeric value.)
- Use the and/or key to change the displayed numeric value to "02", and then press the

key once to specify the digital operator as the operating device to input operation commands.

1

2

(The display reverts to [A002]. The operating device indicator lamp above the [RUN] key goes on.)

STR

5) Set the output frequency.

- Display the function code "F001" on the monitor screen, and then press the key once.

FUNC

(The monitor shows a preset output frequency. With the factory setting, [0 Hz] is shown.)
- Use the and/or key to change the displayed numeric value to the desired output frequency,

and then press the key once to determine the frequency.

(The display reverts to [F001].)

6) Set the operation direction of the motor.

- Display the function code "F004" on the monitor screen, and then press the key once.

FUNC

1

2

STR

(The monitor shows "00" or "01".)