Chapter 4 Explanation of Functions

(3) Free V/f characteristic setting
The free V/f characteristic setting function allows you to set an arbitrary V/f characteristic by specifying the
voltages and frequencies (b100 to b113) for the seven points on the V/f characteristic curve.
The free V/f frequencies (1 to 7) set by this function must always be in the collating sequence of "1

≤ 2 ≤ 3

≤ 4 ≤ 5 ≤ 6 ≤ 7".
Since all free V/f frequencies are set to 0 Hz as default (factory setting), specify their arbitrary values
(begin setting with free-setting V/f frequency (7)). (The inverter cannot operate with the free V/f
characteristic in the factory setting.)
Enabling the free V/f characteristic setting function disables the torque boost selection (A041/A241), base
frequency setting (A003/A203/A303), and maximum frequency setting (A004/A204/A304). (The inverter
assumes the value of free-setting V/f frequency (7) as the maximum frequency.)

Item Function

code

Data

Description

Free-setting V/f frequency (7)

b112

0.to 400.(Hz)

Free-setting V/f frequency (6)

b110

0. to free-setting V/f frequency (7) (Hz)

Free-setting V/f frequency (5)

b108

0. to free-setting V/f frequency (6) (Hz)

Free-setting V/f frequency (4)

b106

0. to free-setting V/f frequency (5) (Hz)

Free-setting V/f frequency (3)

b104

0. to free-setting V/f frequency (4) (Hz)

Free-setting V/f frequency (2)

b102

0. to free-setting V/f frequency (3) (Hz)

Free-setting V/f frequency (1)

b100

0. to free-setting V/f frequency (2) (Hz)

Setting of the output

frequency at each

breakpoint of the V/f

characteristic curve

Free-setting V/f voltage (7)

b113

Free-setting V/f voltage (6)

b111

Free-setting V/f voltage (5)

b109

Free-setting V/f voltage (4)

b107

Free-setting V/f voltage (3)

b105

Free-setting V/f voltage (2)

b103

Free-setting V/f voltage (1)

b101

0.0 to 800.0(V)

Setting of the output

voltage at each

breakpoint of the V/f

characteristic curve (*1)

(Example)

f1

f2

f3

f4

f5

f6

f7

0

V2,V3

V1

V5

V6

V7

V4

Output volt

Output frequency (Hz)

age (V)
















*1 Even if 800 V is set as a free-setting V/f voltage (1 to 7), the inverter output voltage cannot exceed the

inverter input voltage or that specified by the AVR voltage select.

Carefully note that selecting an inappropriate control system (V/f characteristic) may result in
overcurrent during motor acceleration or deceleration or vibration of the motor or other machine driven
by the inverter.

0

f6

f7

V6

V7

Voltage that can be output by the
inverter or that was specified by
the AVR voltage select

Output frequency (Hz)

Output voltage (V)










4 -