Chapter 4 Explanation of Functions

4 -

69

4.2.72 Low-current indication (LOC) signal

C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
C038: Low-current indication signal output mode selection
C039: Low-current indication signal detection level

Related code

The inverter outputs the low-current indication (LOC)
signal when the inverter output current falls to the
low-current indication signal detection level (C039) or
less.
You can select one of the two signal output modes with the low-current indication signal output mode
selection (C038). In one mode, the LOC signal output is always enabled during the inverter operation. In
the other mode, the LOC signal output is enabled only while the inverter is driving the motor for
constant-speed operation.

Item

Function code

Data or range of data

Description

Terminal function

C021 to C025

Alarm relay terminal function

C026

43

LOC: Low-current indication signal

00

Enabling the signal output during
operation

Low-current indication signal
output mode selection

C038

01

Enabling the signal output only
during constant-speed operation (*1

Low-current indication signal
detection level

C039

0.0 to "2.0 x rated

current" (A)

Setting of the threshold current level
at which to output the low-current
indication signal

(*1) When 01 (control circuit terminal) is selected as frequency source setting (A001), there is a case that
inverter does not recognize the speed as constant value due to sampling. In this case, adjusting is to be
made by setting C038=00 (valid during operation) or increasing analogue input filter (A016).



4.2.73 Inverter ready signal (IRDY)

Output current (A)

Low-current indication
signal detection level
(C039)

Low-current
indication signal

ON

ON






Item

The inverter outputs the inverter ready (IRDY) signal when it is ready for
operation (i.e., when it can receive an operation command).

C021 to C0

- The inverter can recognize only the operation command that is input while the IRDY signal is output.

25: Terminal [11] to [15] functions

C026: Alarm relay terminal function

Related code

- If the IRDY signal is not output, check whether the input power supply voltage (connected to the R, S, and T
terminals) is within the range of specification.
- Signal is not output when the power is given only to control power supply.

Function code

Data or range of data

Description

Terminal function

C021 to C025

Alarm relay terminal function

C026

50

IRDY: Inverter ready signal

4.2.74 Forward rotation signal (FWR)

The FWR signal is turned off while the inverter is driving the motor for
reverse operation or stopping the motor.

The inverter continues to output the forward rotation (FWR) signal while
it is driving the motor for forward operation.

C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function

Related code

Item

Function code

Data or range of data

Description

Terminal function

C021 to C025

Alarm relay terminal function

C026

51 FWR:

Forward

rotation

signal