Chapter 4 explanation of functions – Hitachi SJ700-2 User Manual

Page 193

Advertising
background image

Chapter 4 Explanation of Functions

4 - 13

0

(2) Positive and negative responses
(i) Positive response
- Response frame
Frame format

STX Station

No. ACK

BCC

CR

Description

Data

size

Setting

STX

Control code (Start of TeXt)

1 byte

STX (0x02)

Station No.

Station number of control-target
inverter

2 bytes

01 to 32

ACK

Control code (acknowledgement)

1 byte

ACK (0x06)

BCC

Block check code

2 bytes

XOR of the items from "Station No." to "ACK."
See Item (3) of this section.

CR

Control code (Carriage Return)

1 byte

CR (0x0D)


(ii) Negative response
- Response frame
Frame format

STX

Station No.

NAK

Error code

BCC

CR

Description

Data

size

Setting

STX

Control code (Start of TeXt)

1 byte

STX (0x02)

Station No.

Station number of control-target
inverter

2 bytes

01 to 32

NAK

Control code (negative
acknowledgement)

1 byte

NAK (0x15)

Error code

Content of communication error

2 bytes

See Note 13.

BCC

Block check code

2 bytes

XOR of the items from "Station No." to "Error
code." See Item (3) of this section.

CR

Control code (Carriage Return)

1 byte

CR (0x0D)


Note 15: Error codes

Error code

Description

01H Parity

error

02H

Sum check error

03H Framing

error

04H Overrun
05H Protocol

error

06H

ASCII code error

07H Receiving-buffer

overflow

08H Reception

timeout

- -
- -

11H Command

error

12H -
13H Execution

disabled

14H -
15H -
16H Parameter

error

17H -

If a command is broadcasted to all inverter stations, no response will be returned to the external control
system.

Advertising