Chapter 4 Explanation of Functions

4.2.4 Frequency source setting

A001: Frequency source setting

Related code

The frequency source setting function allows you to select the method to
input the frequency-setting command.

Motor rotation direction is inverted when -10 to 0V is given as frequency
command to 02-L terminals.

Item Function

code

Data

Description

(00)

(Valid only when the OPE-SR is used)
Use the control provided on the digital operator to set the frequency.

01

Input the frequency-setting command via a control circuit terminal (0-L,
OI-L, or O2-L).

02

Use the digital operator (function "F001") or remote operator to set the
frequency.

03

Input the frequency-setting command via an RS485 communication
terminal.

04

Input the frequency-setting command from the board connected to
optional port 1.

05

Input the frequency-setting command from the board connected to
optional port 2.

06

Use the SJ-FB to input the frequency-setting command as a pulse train
(see 4.2.21)

07

Use the SET-Freq command of the easy sequence function as the
frequency-setting command.

Frequency
source
setting

A001

10

Use the operation result of the set frequency operation function as the
frequency-setting command. (see 4.2.12)

4.2.5 Run command source setting

A002: Run command source setting
C001 to C008: Terminal [1] to [8] functions
C019: Terminal [FW] active state
F004: Keypad Run key routing

Related code

The run command source setting function allows you to select the
method to input operation commands (to start and stop the motor).
As the operation commands via control circuit terminals, turn the
FW signal (for forward operation) or RV signal (for reverse
operation) on and off to start and stop the motor, respectively.
(Note that the factory setting assigns the FW signal to intelligent input terminal [8].)
To switch each intelligent input terminal between a and b contacts, specify each terminal with function
"C011" to "C019", and then perform input a/b (NO/NC) selection for each terminal.
When using the digital operation for the inverter operation, specify the desired motor operation direction
with function "F004", and use the RUN and STOP/RESET keys to start and stop the motor, respectively.
If the start commands for both forward and reverse operations are input at the same time, the inverter will
assume the input of a stop command.

Item Function

code

Data

Description

01

Input the start and stop commands via control circuit
terminals (FW and RV).

02

Input the start and stop commands from the digital or
remote operator.

03

Input the start and stop commands via RS485
communication terminals.

04

Input the start and stop commands from option board 1.

Run command
source setting

A002

05

Input the start and stop commands from option board 2.

00

a (NO) contact

Terminal [FW]
active state

C019

C011 to C018

01

b (NC) contact

Note 1: If function "31" (forcible operation) or "51" (forcible-operation terminal) is assigned to an intelligent

input terminal, the settings made with functions "A001" and "A002" will be invalidated when the
said intelligent input terminal is turned on and those methods to input frequency-setting and
operation commands which are specified for the said terminal will be enabled.

Note 2: On the remote operator (SRW) being used to operate the inverter, pressing the REMT (remote)

key enables you to input both frequency-setting and operation commands from the remote
operator.