Chapter 4 explanation of functions, 39 intelligent input terminal setting – Hitachi SJ700-2 User Manual

Page 109

Advertising
background image

Chapter 4 Explanation of Functions

4.2.39 Intelligent input terminal setting

C001 to C008: Terminal [1] to [8] functions

Related code

You can assign the functions described below to intelligent input
terminals [1] to [8]. To assign the desired functions to the
terminals, specify the desired data listed in the table below for
terminal settings "C001" to "C008". For example, "C001"
corresponds to intelligent input terminal [1].
You can select the a-contact or b-contact input for individual intelligent input terminals.
You can assign one function only to an intelligent input terminal. If you have attempted to assign a function
to two or more intelligent input terminals, the function is assigned to only the terminal to which you have
last attempted assignment. Function data "NO" (no assign) is assigned to other terminals, and those
terminals are ineffective in terms of functions.
After assigning the desired functions to intelligent input terminals [1] to [8], confirm that the assigned
functions have been stored on the inverter.

Function code

Data

Description

Reference item

Page

01

RV: Reverse RUN command

Operation command

02

CF1: Multispeed 1 setting (binary operation)

03

CF2: Multispeed 2 setting (binary operation)

04

CF3: Multispeed 3 setting (binary operation)

05

CF4: Multispeed 4 setting (binary operation)

Multispeed operation function

4-47

06

JG: Jogging

Jogging operation function

4-49

07

DB: External DC braking

DC braking (external DC braking) function

4-20

08

SET: Set 2nd motor data

2nd/3rd motor control function

4-50

09

2CH: 2-stage acceleration/deceleration

2-stage acceleration/deceleration function

4-30

11

FRS: Free-run stop

Free-run stop function

4-52

12

EXT: External trip

External trip function

4-57

13

USP: Unattended start protection

Unattended start protection function

4-56

14

CS: Commercial power source enable

Commercial power supply switching function

4-53

15

SFT: Software lock (control circuit terminal block) Software lock function

4-51

16

AT: Analog input voltage/current select

External analog input setting function

4-12

17

SET3: 3rd motor control

2nd/3rd motor control function

4-50

18 RS:

Reset

Reset

4-54

20

STA: Starting by 3-wire input

21

STP: Stopping by 3-wire input

22

F/R: Forward/reverse switching by 3-wire input

3-wire input function

4-57

23

PID: PID disable

24

PIDC: PID reset

PID function

4-26

26

CAS: Control gain setting

Control gain switching function

4-58

27

UP: Remote control UP function

28

DWN: Remote control DOWN function

29

DWN: Remote control data clearing

Remote control (UP/DWN) function

4-56

31

OPE: Forcible operation

Forcible-operation function

4-51

32

SF1: Multispeed 1 setting (bit operation)

33

SF2: Multispeed 2 setting (bit operation)

34

SF3: Multispeed 3 setting (bit operation)

35

SF4: Multispeed 4 setting (bit operation)

36

SF5: Multispeed 5 setting (bit operation)

37

SF6: Multispeed 6 setting (bit operation)

38

SF7: Multispeed 7 setting (bit operation)

Multispeed operation function

4-47

39

OLR: Overload restriction selection

Overload restriction function

4-39

40

TL: Torque limit enable

41

TRQ1: Torque limit selection bit 1

42

TRQ2: Torque limit selection bit 2

Torque limitation function

4-92

43

PPI: P/PI mode selection

P/PI switching function

4-58

44

BOK: Braking confirmation

Brake control function

4-81

45 ORT:

Orientation

Orientation

function

4-96

46

LAC: LAD cancellation

LAD cancellation function

4-10

47

PCLR: Clearance of position deviation

48

STAT: Pulse train position command input enable

V2 control mode selection function

4-96

C001 to C008

50

ADD: Trigger for frequency addition (A145)

Frequency addition function

4-14

4 -

46

Advertising