Chapter 4 explanation of functions, 26 energy-saver operation – Hitachi SJ700-2 User Manual

Page 95

Advertising
background image

Chapter 4 Explanation of Functions

(2) Curve constant (swelling degree)

Specify the swelling degree of the acceleration curve with reference to the following graphs:


4 - 3

2













The acceleration or deceleration time may be shortened midway through the acceleration or deceleration
according to the S-curve pattern.
If the LAD cancellation (LAC) function has been assigned to an intelligent input terminal and the LAC
terminal is turned on, the selected acceleration and deceleration patterns are ignored, and the output
frequency is quickly adjusted to that specified by the frequency command.

(3) Curvature of EL-S-curve pattern

When using the EL-S-curve pattern, you can set the curvatures (A150 to A153) individually for
acceleration and deceleration.

If all curvatures are set to 50%, the EL-S-curve pattern will be equivalent to the S-curve pattern.












4.2.26 Energy-saver operation

The energy-saver operation function allows you to automatically minimize
the inverter output power while the inverter is driving the motor at
constant speed. This function is suited to operating a fan, pump, or other
load that has a reduced-torque characteristic.
To use this function, specify "01" for the operation mode selection (A085).
Use the energy saving mode tuning function (A086) to adjust the response and accuracy of the
energy-saver operation.
The energy-saver operation function controls the inverter operation comparatively slowly. Therefore, if a
sudden change in the load occurs (e.g., impact load is applied), the motor may stall, and, consequently,
the inverter may trip because of overcurrent.

Item Function

code

Data

Description

00 Normal

operation

01 Energy-saving

operation

Operation mode selection

A085

02 Fuzzy

operation

Item Function

code

Data

Response

Accuracy

Energy saving mode tuning

A086

0

100

Slow

Quick

High

Low

96.9
82.4

17.6

3.1

25 50

75

10

02

10 02

99.6
93.8

35

25

50

75

10

10

02

87.5
68.4
64.6

65

35.4

0.39

25

50

75

10

02

31.6

12.5
6.25

Output frequency (Hz)

Output frequency (Hz)

Output frequency (Hz)

rget

y

(100%)

Target
frequency
(100%)

Target
frequency
(100%)

Acceleration time (100%) to reach
the set output frequency

Acceleration time (100%) to reach
the set output frequency

Acceleration time (100%) to reach
the set output frequency

Time Time Time

A085: Operation mode selection
A086: Energy saving mode tuning

Ta
frequenc

Related code

100

50

Time (s)

Output frequency rate (%)

Curvature for
acceleration 2
(A151)

Curvature for
deceleration 1
(A152)

Curvature for
deceleration 2
(A153)

Curvature for
acceleration 1 (A150)