Chapter 2 installation and wiring – Hitachi SJ700-2 User Manual

Page 42

Advertising
background image

Chapter 2 Installation and Wiring

(4) Recommended cable gauges, wiring accessories, and crimp terminals

Note: For compliance with CE and UL standards, see the safety precautions concerning EMC and the

compliance with UL and CUL standards under Safety Instructions.

The table below lists the specifications of cables, crimp terminals, and terminal screw tightening
torques for reference.

Applicable device

Motor

output

(kW)

Applicable inverter

model

Gauge of power
line cable (mm

2

)

(Terminals: R, S,

T, U, V, W, P, PD,

and N)

Grounding

cable (mm

2

)

External braking

resistor across

terminals P and

RB (mm

2

)

Size of

terminal

screw

Crimp

terminal

Tightening

torque

(N-m)

Earth-leakage
breaker (ELB)

Magnetic
contactor

(MC)

5.5 SJ700-055LFF2

5.5

5.5 5.5

M5

R5.5-5

2.4

EX50B

(50A)

HK25

7.5 SJ700-075LFF2

8

8

8

M5 R8-5 2.4

EX60

(60A)

HK35

11 SJ700-110LFF2

14

14

14

M6 R14-6 4.5 RX100

(75A) HK50

15 SJ700-150LFF2

22

22

22

M6 22-6 4.5 RX100

(100A) H65

18.5 SJ700-185LFF2

30

22

30

M6

30-S6

38-8

4.5 RX100

(100A) H80

22 SJ700-220LFF2

38

30

38

M8

38-S8

38-10

8.1 RX225B

(150A) H100

30 SJ700-300LFF2 60

(22×2) 30

― M8

60-S8

60-10

CB60-8

CB60-S8

8.1 RX225B

(200A) H125

37 SJ700-370LFF2 100

(38×2) 38

― M8

100-8

8.1

RX225B

(225A)

H150

45 SJ300-450LFF2 100

(38×2) 38

― M8

100-8

8.1

RX225B

(225A)

H200

200 V

cl

ass

55 SJ300-550LFF2 150

(60×2) 60

― M10

150-10

8.1

RX400B

(350A)

H250

5.5 SJ700-055HFF2

2

2

2

M5 R2-5 2.4

EX50C

(30A) HK20

7.5 SJ700-075HFF2

3.5

3.5 3.5

M5

3.5-5

2.4

EX50C

(30A)

HK25

11 SJ700-110HFF2

5.5

5.5

5.5

M6 R5.5-6 4.5 EX50C

(30A) HK35

15 SJ700-150HFF2

8

8

8

M6 8-6

4.5 EX60B

(60A) HK35

18.5 SJ700-185HFF2

14

14

14

M6 14-6

4.5

EX60B

(60A)

HK50

22 SJ700-220HFF2

14

14

14

M6 14-6 4.5 RX100

(75A) HK50

30 SJ700-300HFF2

22

22

― M6

22-6

4.5

RX100

(100A)

H65

37 SJ700-370HFF2

38

22

― M8

38-8

8.1

RX100

(100A)

H80

45 SJ700-450HFF2

38

22

― M8

38-8

8.1

RX225B

(150A)

H100

400 V

cl

ass

55 SJ700-550HFF2

60

30

― M8

R60-8

8.1

RX255B

(175A)

H125

Note: Cable gauges indicate those of HIV cables (maximum heat resistance: 75°C).

(5) Connecting the control circuit to a power supply separately from the main circuit

If the protective circuit of the inverter operates to open the magnetic contactor in the input power
supply circuit, the inverter control circuit power is lost, and the alarm signal cannot be retained.

To retain the alarm signal, connect control circuit terminals R0 and T0 to a power supply.

In details, connect the control circuit power supply terminals R0 and T0 to the primary side of the
magnetic contactor as shown below.
(Connection method)
Power-receiving specifications

② Remove the J51 connector.

① Remove the connected cables.

③ Connect the control circuit power

supply cables to the control
circuit power supply terminal
block.

J51

200 V class model:
200 to 240 V (+10%, -15%)
(50/60 Hz ±5%)
(282 to 339 VDC)
400 V class model:
380 to 480 V (+10%, -15%)
(50/60 Hz ±5%)
(537 to 678 VDC)

Note the following when connecting separate power supplies to control circuit power supply terminals
(R0 and T0) and main circuit power supply terminals (R, S, and T):

- Use a cable thicker than 1.25 mm

2

to connect the terminals R0 and T0 (terminal screw size: M4).

- Connect a 3 A fuse in the control circuit power supply line.
- If the control circuit power supply (connected to R0 and T0) is turned on earlier than the main circuit

power supply (connected to R, S, and T), ground fault is not checked at power-on.

- When supplying DC power to the control circuit power supply terminals (R0 and T0), specify "00" as

the "a/b (NO/NC)" selection (function code C031 to C036) for intelligent output terminals ([11] to
[15]) and intelligent relay terminals (AL0, AL1, and AL2). If "01" is specified as the "a/b (NO/NC)"
selection, output signals may chatter when the DC power supply is shut off.

2 - 20

Advertising