Chapter 4 Explanation of Functions

Item

Function code

Data or range of data

Description

33

LOG1: Logical operation result 1
(C142, C143, and C144)

34

LOG2: Logical operation result 2
(C145, C146, and C147)

Terminal function

35

LOG3: Logical operation result 3
(C148, C149, and C150)

36

LOG4: Logical operation result 4
(C151, C152, and C153)

37

LOG5: Logical operation result 5
(C154, C155, and C156)

Alarm relay
terminal function

C021 to C025

C026

38

LOG6: Logical operation result 6
(C157, C158, and C159)

Logical output
signal selection 1

C142/C145/C148/

C151/C154/C157

Selection of "00" to "56" from the

data (except LOG1 to LOG6) output

to intelligent output terminals

Selection of operation-target 1

Logical output
signal selection 2

C143/C146/C149/

C152/C155/C158

Selection of "00" to "56" from the

data (except LOG1 to LOG6) output

to intelligent output terminals

Selection of operation-target 2

00 AND
01 OR

Logical output
signal operator
selection

C144/C147/C150/

C153/C156/C159

02 XOR

4.2.67 Capacitor life warning signal (WAC)

C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function

Related code

The inverter checks the operating life of the capacitors on the
internal circuit boards on the basis of the internal temperature
and cumulative power-on time.
You can monitor the state of the capacitor life warning (WAC) signal by using the life-check monitoring
function (d022).
If the WAC signal is output, you are recommended to replace the main circuit and logic circuit boards.

Item

Function code

Data or range of data

Description

Terminal function

C021 to C025

Alarm relay terminal function

C026

39

WAC: Capacitor life warning signal
(for on-board capacitors)

4.2.68 Communication line disconnection signal (NDc)

This signal function is enabled only when ModBus-RTU has been
selected for the RS485 communication.

C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
C077: Communication trip time

Related code

If a reception timeout occurs, the inverter continues to output the
communication line disconnection signal until it receives the next
data.
Specify the limit time for reception timeout by setting the communication trip time (C077).
For details, see Section 4.4, "Communication Functions."

(C077)

External control equipment

Inverter

Monitoring timer

Communication line
disconnection signal (NDc)

Communication trip time










Item

Function code

Data or range of data

Description

Terminal function

C021 to C025

Alarm relay terminal function

C026

32

NDc: Communication line
disconnection signal

Communication trip time

C077

0.00 to 99.99 (s)

Setting of the limit time for
reception timeout

4 -